12
|
CONVERSION INSTRUCTIONS
ILL1060-D
Ensure the switch screw is fully inserted and switch the
CPMD Control Box isolation switch to the “ON” position.
ILL1243-A
Plug in and turn on the mains power to the MobileMAX
cooler.
COMMISSIONING THE COOLER
FAULT CODES
The following information allows quick diagnosis at start
up -
The “Tricolour LED” on the CPMD (under the rubber
splash cover) acts as a general diagnostic indicator, and
will function as follows:
Green double flash every 2 seconds indicates the CPMD
control is running normally.
If it does not glow at all, then there is either no power to
the CPMD Electronics Module (check isolating switch,
circuit breaker, plug and socket connection, or a failure
has occurred).
Red flashing of the left hand Tricoloured LED indicates
one or more of the following fault codes are present:
• 1 Red Flash indicates Fault Code #1
-
Communication Failure.
• 2 Red Flashes indicates Fault Code #2
- Failure to
detect water at probes. (Only for coolers fitted with
solenoid, probes and drain valve).
• 4 Red Flashes indicates Fault Code #4
- Failure to
clear probes during drain. (Only for coolers fitted with
solenoid, probes and drain valve).
• 7 Red Flashes indicates Fault Code #7
- Incorrect
Supply Frequency.
ILL1014-D
Tri-
Colour
Red
Red
Brn
Blue
Blk
Brn
Blue
CORRECT PLUG ORIENTATION
ILL1014-D