UR46-81/82S
Options
Document number: SG104148TEN
Revision: B01
Issue date: 20.8.2012
Copyright© 2012 Sécheron SA - This document is not contractual and contains information corresponding to the level of technology at the date of release.
File: g-UR46-8S_options_en.fm
G-57
G.
Options
G.1
Manual closing device
G.1.1
Description
Mounted at the rear of the closing device (1), the manual closing device (2) enables the customer
to close the circuit-breaker manually.
G.1.2
Maintenance
Removal
a) Remove the four screws (1) holding the flange (2) and the cover (3).
b) Remove the complete manual closing device (5).
c) Remove the cylinder (6) and cover (3).
Reassembling
d) Insert the cover (3), taking care that the flange (4) does not move.
e) Hold the cover (3) and insert the cylinder (6) with its spring (7) and insert the manual closing
device (5).
f)
Screw the unit together with the four M6 screws (1), taking care that the flange (4) does not
move: hold the cover (3) firmly in this position and turn the manual closing device (5) until the
pivot (8) and the lever (9) can be operated vertically from top to bottom.
g) Tighten the four M6 screws (1) to a torque of 9 Nm.
03632-1
G.1.3
Spare part catalogue
Refer to the figure above.
DANGER!
To ensure maximum safety, servicemen and operators must read the
A.2 "Safety
precautions"
section before starting installation, maintenance and adjustment of
the device or before starting to operate it.
Important!
Do not change the position of the flange (4) while working.
Mark its position with a felt-tip pen before removing the moving core assembly.
Pos.
Part number
SP
Description
Qty
9
HSBR430708P0001
x
Lever
1
3
2
4
5
1
2
6
7
3
8
9
1
5