STS11 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (CONTINUED)
50
Installer
Setup
Number
Installer Setup
Name
Settings Notes
Initial
Setting
Record
0530
Adaptive Intelligent
Recovery
1-Adaptive Intelligent Recovery control is
activated (system starts early so set-point is
reached by start of program period).
0-Conventional Recovery (system starts
recovery at programmed time)
IF “0” is selected
Setup 0680 and 0690 are
not selectable
0540 Number
of
Periods
2-two periods available (Wake and Sleep)
4-four periods available (Wake, Leave,
Return and Sleep)
Not shown if non-
programmable is selected.
2 or 4 applies to all days of
the week. When it is
changed the schedule
must be reprogrammed.
0580
Minimum
Compressor
Off Time
5-five-minute compressor off-time setting
(factory setting)
0, 2, 3, 4-other compressor off-time settings
Compressor delay is a
make signal on all
start-up. Display will
indicate "Wait" when
activated. Recommend
Minimum Compressor Off
Time. See page 80.
0600
Heat Temperature
Range Stop
40-90-temperature range (1°F increments)
of heating set-point.
Shown in 1/2 °C.
0610
Cool Temperature
Range Stop
50-99-temperature range (1°F increments)
of cooling set-point.
Shown in 1/2 °C.
0640 Clock
Format
12-12 hour clock (factory setting)
24-24 hour clock
STS11 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (CONTINUED)
51
Installer
Setup
Number
Installer Setup
Name
Settings Notes
Initial
Setting
Record
0650
Extended Fan On
Time
Heat
0-no extended fan operation after call for
heat ends
90- fan operation is extended 90 seconds
after call for heat ends.
Not shown if fan operation
is set to fossil fuel or in
Cool Only Systems
0660
Extended Fan On
Time
Cool
0.no extended fan operation after call for
cool ends
90.fan operation is extended 90 seconds
after call for cool ends.
Not shown in Heat Only
Systems.
0670 Keypad
Lockout
0-unlocked keypad
1-partially locked keypad
2-fully locked keypad
Unlocked all functions are
available. Partially locked
only.
Temperature up and down
keys and ability to enter
and modify Installer Setup
mode are available.
Fully locked only ability to
enter and modify Installer
Setup mode are available.
0680
Temperature
Control in Heat
1- Highest energy savings.
2- Moderate energy savings.
3- Least energy savings.
Default setting is # 1