- 6 -
thermostat will automatically exit to the
OFF
mode. Note: All changes made in the
configuration menu are automatically saved.
CONFIGURATION MENU CHART
See “Parameters” section for a detailed explanation of parameters and values.
PARAMETERS
CC - Select Cooling Cycle Rate
The FA setting produces shorter cooling cycles. The SL setting produces longer cooling
cycles. FA cycles the system at a 0.75ºF differential (0.5°C), and SL cycles the system at a
1.5ºF differential (1°C).
HC - Select Heating Cycle Rate
The FA setting produces shorter heating cycles. The SL setting produces longer heating
cycles. FA cycles the system at a 0.75ºF differential (0.5°C), and SL cycles the system at a
1.5ºF differential (1°C).
CP - Select Compressor Lockout Delay
To protect the compressor from short cycling, you can select the minimum length of time the
compressor will turn off between cycles from 0 to 5 minutes in 1 minute increments. When a
compressor lockout delay occurs, “COMP DELAY” will flash.
Parameter
Parameter
Value
Options
Description
Factory
Defaults
CC
FA or SL
Select cooling cycle rate:
FA= fast SL = slow
FA
HC
FA or SL
Select heating cycle rate:
FA= fast SL = slow
FA
CP
0 to 5
Select compressor lockout delay:
0 = none, 1 to 5 = number of minutes delayed after last call
5
AU
1 to 10
Select auxiliary heat offset:
1to 10 = number of degrees below setpoint
4
bL
1, 2, or 3
Select LCD backlight duration:
(1) = OFF (2) = 30 seconds after any button push (3) = always ON
2
FL
00, 1 to 12
Select filter service time:
00 = deactivated 1 to 12 = number of months (1 month = 30 days)
00
FC
F or C
Select temperature scale:
F = ° Fahrenheit C = ° Celsius
F
CL
-4 to 4
Select temperature calibration value:
-4 to 4 = number of degrees above or below room temperature
0