background image

 

- 8 - 

SYSTEM CHECK

 

If at any time during testing your system does not operate properly, contact a qualified HVAC 
contractor.     

Ensure that there is power to the system.     

Fan Operation 

(If your system does not have a “G” (Fan) terminal connection, skip to the “Heating System” 
section.) 

1.  Move the 

SYSTEM

 switch to the 

OFF

 position.   

2.  Move the

 FAN

 switch to the

 ON

 position. The blower should begin to operate.   

3.  Move the 

FAN

 switch to the 

AUTO

 position. The blower should stop immediately. 

Heating System 

1.  Move the 

SYSTEM

 switch to the 

HEAT

 position. If the auxiliary heating system has a 

standing pilot, be sure to light it. 

2.  Adjust the setpoint to a temperature above the current room temperature.   

 If the (FA)st heating cycle rate is selected in the configuration menu (see 

“Configuration 

Menu Chart

”), the thermostat will call for heat when the room temperature is 0.75ºF (0.5ºC) 

below setpoint and turn off at setpoint. 

 If the (SL)ow heating cycle rate is selected, the thermostat will call for heat when the room 

temperature is 1.5ºF (1ºC) below setpoint and turn off at setpoint. 

 The auxiliary heat will activate when the room temperature is below the setpoint by the 

auxiliary heat offset value (AU) plus heating cycle rate value (HC), as established during 
configuration. When auxiliary 

heat turns on “AUX” will be displayed. (See “Configuration 

Menu Chart”, “Parameters”, and Figure 1.) 

* Note: Auxiliary heat will only activate in conjunction with the compressor and fan and 
therefore will be affected by compressor lockout delay settings

. (See “Configuration 

Menu Chart”) Once activated, auxiliary heat will continue to run until the room 
temperature is less than 2°F (1°C) below setpoint, and the first stage of heat will 
complete the call. 

3.  When the thermostat calls for heat, 

  will display. If 

  is not displayed and 

“COMP 

DELAY” is flashing, the compressor lockout delay feature is operating in the heat pump 
mode. (See 

“Configuration Menu Chart”) 

Emergency Heating System 

The Emergency Heat System bypasses the heat pump to use the heat source connected to 
termina

l “E” on the thermostat. It is typically used when compressor operation is not desired or 

you prefer to use the backup heating system only.   

1.  Move the 

SYSTEM

 switch to the 

EMH

 position. 

“EMH” will flash on the display as long as 

Summary of Contents for SN12I

Page 1: ...Safety Information 1 Remove the Old Thermostat 3 Install the New Thermostat 4 Configuration 5 Configuration Menu Chart 6 Parameters 6 System Check 8 Basic Thermostat Operation 9 Troubleshooting 10 Wa...

Page 2: ...n clock function IMPORTANT SAFETY INFORMATION Use a professional contractor to install this thermostat Read all of the information in this manual before installing this thermostat WARNING Electrical S...

Page 3: ...vice Reminder Time Day Setting Low Battery Icon Configuration Compressor Lockout Delay SET TO AM MON SERVICE FILTER CONFIG COMP DELAY ON AUTO AUX EMH Figure 1 THERMOSTAT BUTTONS AND SWITCHES Figure 2...

Page 4: ...OFF position 3 Remove the cover of the old thermostat This should expose the wires 4 Label the wires from the existing thermostat using the enclosed wire markers and record in the chart below before r...

Page 5: ...ing screws and anchors provided mount the thermostat base loosely to the wall or junction box See Figure 3B 6 Place a level against the bottom of the base and adjust until level then tighten the screw...

Page 6: ...the battery compartment Install two fresh AA alkaline batteries in the battery compartment CAUTION Installing batteries backwards can damage the thermostat Be sure to match positive and negative ends...

Page 7: ...compressor from short cycling you can select the minimum length of time the compressor will turn off between cycles from 0 to 5 minutes in 1 minute increments When a compressor lockout delay occurs CO...

Page 8: ...the number of days is also displayed in the upper left corner of the LCD A selection of 00 will deactivate this feature When SERVICE FILTER is displayed in EMH HEAT or COOL mode it can be cleared by...

Page 9: ...ow setpoint and turn off at setpoint The auxiliary heat will activate when the room temperature is below the setpoint by the auxiliary heat offset value AU plus heating cycle rate value HC as establis...

Page 10: ...e SL ow cooling cycle rate is selected the thermostat will call for cooling when the room temperature is 1 5 F 1 C above setpoint and turn off at setpoint 3 When the thermostat calls for cooling will...

Page 11: ...e If no buttons are pressed within 15 seconds the thermostat will exit to normal operation 4 In filter review mode press and hold the and buttons at the same time to reset the amount of time until the...

Page 12: ...itations or ex clusion may not a pply to you INTERNATIONAL REFRIGERATION PRODUCTS CO INC LIMITED WARRANTY POLICY INTERNATIONAL REFRIGERATION PRODUCTS CO INC Langhorne PA 19047 www irproducts biz INTE...

Reviews: