There are four primary components to be installed:
1. The 931 EntryCheck
™
should be mounted on the wall
adjacent to the door. It should be on the same side as the
door strike and about 4 feet above the floor.
2. The Control Module should be mounted inside the building
near a power source. Typically the control module is hidden in
a false ceiling or closet. The control module must be located
in an environmentally controlled area where the temperature
remains between -40°C and +49°C ( -40°F and 125°F)
3. The Wiring Cable connects the keypad to the control module.
It is important not to locate the cable adjacent to any wiring
that carries line voltage. Included with the system is a 15-foot
TWC-15 12 conductor jacketed wiring cable of which only 11
wires are used. If the Control Module must be located further
than 15 feet from the Keypad, additional cable may be
spliced. The maximum distance between the Keypad and the
Control Module must not exceed 1,000 feet. For runs over
200 feet, 18 gauge wire should be used. Under 200 feet, 20
gauge is acceptable.
4. The Electric Strike/Other Locking Device (not included)
connects to the 931’s Main Relay output via the strike cable.
(See Appendix B - Typical Wiring Diagrams pg 14)
THE INSTALLATION PROCEDURE
REQUIRED TOOLS
You will need the following tools:
• Medium Phillips screwdriver
•
⅛
" standard screwdriver
• Drill
•
⅞
” or 1” (25mm) drill bit
• ½" (16mm) drill bit
•
5
/
32
" (4mm) drill bit (For 12 Pad 3x4)
•
3
/
16
” (6mm) drill bit (For 5 Pads & Thinline 2x6)
SYSTEM COMPONENTS
PREPARING FOR INSTALLATION
PREPARE THE KEYPAD FOR INSTALLATION
There are different procedures for mounting each Keypad. Locate the Keypad part number on the back of the
Keypad and follow appropriate mounting instructions below. Keypad templates are included with each Keypad
(except KP-4U) to assist with the installation.
Typical Installation
3
2
1
Strike
Cable
4