1. SpecificationS
this appliance and flue were tested with the following minimum clearances.
the Seguin aurore free standing appliance and triple skin flue kit with Solid 8” casing were tested in two
positions in a manner conforming to australian & new Zealand Standards 2918:2018, appendix B.
a minimum
1130mm
deep X
850mm
wide and
9mm
thick non-combustible hearth should be installed,
refer to aS/nZS 2918:2018 3.3 floor protector. the floor protector/hearth should extend
480mm
in front
of the appliance fuel loading door and be placed centrally in the
850mm
width.
clearances & Hearth- Seguin aurore & Saphir
Co
M
bustible W
alls
CoMbustible Walls
675MM
150MM
sWing Door
aPPlianCe
480
MM
hearth
1130
MM
850MM
Position a Parallel Position
diagram not to scale
Position b Corner Position
diagram not to scale
Co
Mbustible W
alls
Co
Mbustible W
alls
hearth
1130
MM
850MM
475MM
sWing Door
iMPortant
Please note this appliance has been tested with the installation of a heat shield. these clearances outlined are
for an appliance with a heat shield installed. if the heatshield is not installed, the clearances will increase to
1.2m from combustiable material/walls as per as/nZs 2918:2018 3.2 Clearances & heat shielding.
475MM
aPPlianCe
480MM