20
step 15: hearth (floor proteCtor)
the hearth must be constructed from masonry or a non
combustible material and must extend 500mm in front of the
appliance, 250mm on either side of the appliance and have a
thickness of 75mm.
step 13: flue installation
the triple skin flue will then be continued into the roof cavity
and above the roof line, as per australian & new Zealand
Standard aS/nZ 2918:2001. there must be a 25mm clearance
around the outer triple skin flue. the flue must extend a
minimum 1m above the roof line and have a 3m diameter
clearance from the top of the cowl to any objects in a
horizontal direction.
**iMPortant**
the flue should not include more than two 45
°
degree bends.
the angle of these bends cannot exceed more than 45
°
and can
have no more than one length of 900mm flue between them.
step 14: front of the enClosure
The front of the enclosure can now be fitted with masonry
bricks, or a layer of 12mm minimum thick heat resistant sheet.
remember to keep an air gap of 25mm from the front of the
unit.
4.1
maSonry BricK inStallation