Bin Control: Optional Installation
The normal bin control is the ice sensor system. A
bin thermostat may be required in some cases, It
must
be field installed
after
the ice machine has
been placed on the bin.
Before starting, remove the front panel and any
baffle in the bin.
1. Place thermostat in machine behind the high
voltage box. Secure to existing holes with two
screws. Locate bin thermostat bulb.
2. Route bulb thru routing tube (located between
the compressor and the reservoir).
3. Connect harness to bin thermostat and to
controller.
4. Locate bin thermostat bracket.
5. Carefully position the thermostat bulb on the
bracket.
6. Fasten the bracket to the bottom of the ice
machine with the two 3-pronged knobs supplied
with the unit.
7. Pull excess capillary tubing into the machine.
8. Return the baffle to the bin and continue with
the installation.
Note: If the machine is located at an altitude higher
than 2,000 ft., adjust the thermostat by removing
the plastic cover and rotating the adjustment screw
per the table.
CME456R
December 2000
Page 6
Bin Thermostat Altitude Correction Table
CW Turns of Range Screw (under plastic cover)
Feet
Turns
Feet
Turns
2000
55
o
8000
340
o
4000
160
o
9000
385
o
Use This Table to Adjust Thermostat
Routing Hole