Loss-of-Potential, Load Encroachment, and Directional Element Logic
4-3
SEL-351 Instruction Manual
L
OAD
-E
NCROACHMENT
L
OGIC
The load-encroachment logic (see Figure 4.2) and settings are enabled/disabled with setting
ELOAD (= Y or N).
The load-encroachment feature allows phase overcurrent elements to be set independent of load
levels. This is especially helpful in bus overcurrent applications. A bus relay sees the cumulative
currents of all the feeders but still has to provide overcurrent backup protection for all these
feeders. If the phase elements in the bus relay are set to provide adequate backup, they often are
set close to maximum bus load current levels. This runs the risk of tripping on bus load current.
The load-encroachment feature prevents this from happening as shown in the example that follows
in this subsection.
Figure 4.2: Load-Encroachment Logic
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...