Inputs, Outputs, Timers, and Other Control Logic
7-3
SEL-311A Instruction Manual
Input Functions
There are
no
optoisolated input settings such as:
IN101
=
IN102
=
Optoisolated inputs IN101 through IN106 receive their function by how their corresponding
Relay Word bits IN101 through IN106 are used in SEL
OGIC
control equations.
Settings Example 1
Figure 7.2: Circuit Breaker Auxiliary Contact and Close Enable Switch Connected to
Optoisolated Inputs IN101 and IN102
The functions for inputs IN101 and IN102 (Figure 7.2) are described in the following
discussions.
Input IN101
Relay Word bit IN101 (Figure 7.2) is used in the settings for the SEL
OGIC
control equation
circuit breaker status setting:
52A = IN101
Connect input IN101 to a 52a circuit breaker auxiliary contact.
If a 52b circuit breaker auxiliary contact is connected to input IN101, the setting is changed to:
52A = !IN101
[!IN101 = NOT(IN101)]
See
Close Logic
in
Section 6: Close Logic
for more information on SEL
OGIC
control equation
setting 52A.
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......