12 

L-01394-4-05 

emergency battery, the emergency battery may be the cause, which might contain insufficient charge 
to be charged in the potentially explosive atmosphere. 
In this case, the emergency battery is to be removed as described in Section 6.3 and to be charged 
separately from the light fitting. With a 6 V charging voltage and 80 mA charging current, a discharged 
battery will be sufficiently charged within just 5 minutes for it to be reinserted into the light fitting, where 
it can continue to charge.  

 

Before commissioning this explosion-proof lighting fitting please check and ensure that: 

 

 the light fitting has been installed according to the regulations and in the allowed operating position. 

 

 the explosion-proof cable glands resp. explosion-proof locking screws are securely fixed in the 

housing (Torques see Chapter 3, Technical Data). 

 the pressing screw of every explosion-proof cable gland is tightened with the required torque 

(Torques see Chapter 3, Technical Data). 

 

 the connection cable has been firmly installed and is not subject to any tension whatsoever. 

 

  the bare conductor is fully inserted into the terminal and that no cable insulation is clamped. 

 

 the light fitting is closed correctly. 

 

 all gaskets are effective. 

 

 

the light fitting is not damaged whatsoever. 

 

5.1  Isolation measurement 

 

For measuring the isolating resistance the test voltage must be put on between the outer conductor 
and the earth conductor or between the neutral conductor and the earth conductor only. 
 
 
 
 
 
 
 
 
 
 
After finishing the isolation test the conductor between the mains and the light fitting must be 
reconnected safely. Before starting operation the connection of the neutral conductor must be safe for 
avoiding any damage whatsoever of the electronic control gear caused by any inadmissible excess-
voltage in case of an unbalanced mains load. (see Chapter 5.2) 

 

5.2  Emergency light unit in 3-phase-operation 

 

The diagram shows the wiring for light fittings or light fitting groups in 3-phase circuits and with a 
common neutral conductor N. 

 
 
 
 
 
 
 
 
 
        Light fittings with emergency light unit 

 

  OK 

 

 

  fault 

 

If the common neutral conductor is interrupted and voltage is present, then light fittings or groups of 
light fittings may be exposed to unacceptably high voltages and consequently the emergency light unit 

Summary of Contents for nD867.12L Series

Page 1: ...ends on the observance of all safety standards Exact knowledge about all applicable regulations and standards is mandatory for installation maintenance and repair of explosion proof equipment especial...

Page 2: ...thermically or electrically or if the light fitting will be subject to any kind of vibrations it is highly recommended to consult the Adolf Schuch GmbH before starting the installation Every structur...

Page 3: ...tected against mechanical and electrostatic attacks whenever the light fitting is open For this reason the LED must not be touched either Due to harmful gases and other corrosive substances e g ammoni...

Page 4: ...out automatically by the emergency light unit takes place at random within a period of 5 to 28 days after the light fitting has been setup All further automatic operational life tests are then carrie...

Page 5: ...val until the next regular operational life test is unaffected During the functionality and operational life tests the light fitting will switch on even if it was previously switched off 2 3 Ascertain...

Page 6: ...5 Instructions for special versions with remote cutoff switch Special versions of these lighting fixtures are equipped to be connected to a remote cutoff switch Through a remote cutoff switch isolated...

Page 7: ...us areas of zones 2 and 22 Explosion protection o II 3 G Ex ec IIC T4 Gc Version without battery box o II 3 G Ex db ec IIC T4 Gc Version with battery box o II 3 D Ex tc IIIC T80 C Dc Certification SH...

Page 8: ...uctor 0 75 1 0 mm 9 mm conductor 1 5 2 5 mm See information label on the front page when having special versions Locking Clamp lockings to be opened by hand as well as one safety closure at each side...

Page 9: ...fitting in an explosive dust atmosphere is depending on the properties of the surrounding dust Please ensure that there will be an adequate difference between the maximum surface temperature of the f...

Page 10: ...ntries which are not used must be closed with the enclosed closure plug see Chapter 3 Technical Data An inlaid dust protective disc if existing must be removed before The conductors must not be damage...

Page 11: ...emergency battery Version with battery box Open the battery box by loosening the locking screws and flip open the lid Remove the protective cap from the connector of the battery cable Attach the conn...

Page 12: ...ect to any tension whatsoever the bare conductor is fully inserted into the terminal and that no cable insulation is clamped the light fitting is closed correctly all gaskets are effective the light f...

Page 13: ...soft fibrous free cloth Pay attention to the following in case of application of this light fitting in dusty atmospheres Dust deposits have got thermal insulation characteristic features It is necess...

Page 14: ...to the presence of a new battery Open and close the lid of the battery box twice within a 60 second period Opening and closing the case must occur within 10 seconds of each other If this procedure is...

Page 15: ...though the connection to the battery still exists In this case the emergency battery is to be removed as described in Section 6 3 and to be charged separately from the light fitting With a 6V charging...

Page 16: ...16 L 01394 4 05 The test certificates are ready to be loaded down from our homepage www schuch de or we shall send it on request Misprints modifications and errors are excepted...

Reviews: