35
B
ATTERY CONFIGURATION
This page displays the battery capacity.
The configuration of the internal and the external battery (Ah) is not available by the display.
To set the internal and the external battery capacity it is necessary to use the configuration software (reserved for service personnel
only).
Battery capacity configuration page
B
ATTERY TEST SCHEDULING
USS3T - USS3M UPS are equipped with a built-in battery test function.
This page enables the user to schedule the automatic battery tests in order to regularly monitor the battery health.
Battery testing configuration page
It is possible to schedule the battery test in three different ways:
Every “n” hours: the UPS will start the battery test at regular intervals, not necessarily at the same time of the day.
Every “n” days (in “n” days, at a certain hour): the UPS will start the test at regular intervals in the same hour of the day.
Every month (at the selected day/hour): the UPS will start the battery test in the selected day of the month.
B
ATTERY LOW TIME
Set the estimated runtime (expressed in minutes between 0 and 255), below which the system displays the battery low alarm and the
buzzer starts to beep.
[Default → 3 min].