16
Operating instructions
Safety light curtain/safety light grid
SLC 420
SLG 420
EN
4.2 Activation of the contactor control (EDM) without PC software
The contactor control can be activated without PC software as of
firmware version 20 in diagnostic mode by means of cable bridges
To activate the EDM function without PC software, proceed in the
following way:
Establish the connections in accordance with the wiring diagram,
see below.
Both outputs OSSD1 and OSSD2 of the light curtain must be
separated from the machine control
S1
E1
24VDC
2
7
1
3
4
The parameter configuration EDM is activated for at least 2 seconds
when the system starts if there is a wire link between OSSD 1
➔
OSSD2
and a +24V level on the input restart interlock
The active operating mode parameterisation is signalled by the cyclical
changing of the red, yellow and green LEDs until the restart interlock
button is no longer being pressed
The parameterisation can now be made by pressing the button
• If the red and greed LEDs flash at the same time, this indicates that
the EDM function is active, if only the red LED flashes then the EDM
function is not active
• Holding down the button from 2.5 to 6 seconds changes the state of
the EDM function between active and not active and saves the current
selection
After the parameterisation, the link OSSD1
➔
OSSD2 is to be removed
and a system start is to be carried out (+ 24V, OFF/ON) If the EDM
function is parameterised with the wire link, the max value of 500 ms is
set for the signal delay This value can be adjusted using the PC software
/ NSR-0801
If the parameterisation is missing the process can be repeated
4.3 Connector configuration Receiver, Transmitter & Cable
RECEIVER
SLC: Connector
male M12 / 8 pol.
Signal
Designation
Description
5
8
4
3
2
1
7
6
1 WH Restart
Input
2 BN 24 VDC
Power supply
3 GN OSSD 1
Safety output 1
4 YE OSSD 2
Safety output 2
5 GY Diagnostic IN
Input diagnostic data
6 PK Diagnostic OUT Output Diagnostic data
7 BU 0 VDC
Power supply
8 RD Contactor
control EDM
Input
Cable: Connector
female M12 / 8 pole
5
8
4
3
2
1
7
6
TRANSMITTER
SLC: Connector
male M12 / 4 pol.
Signal
Designation
Description
3
2
1
4
1 BN 24 VDC
Power supply
2 WH Diagnostic IN
Input diagnostic data
3 BU 0 VDC
Power supply
4 BK Diagnostic OUT Output Diagnostic data
Cable: Connector
female M12 / 4 pole
3
2
1
4
The colour codes are only valid for the cable types
mentioned below "optional accessories"