15
SLC 420
SLG 420
Operating instructions
Safety light curtain/safety light grid
EN
4. Electrical connection
4.1 Wiring example default
5
Kn 1
Kn 2
S 1
K 1
K 2
6
1
8
2
7
3
4
Schüt
zkontr
olle/EDM
(RD)
DIAG
IN
(WH)
DIAG
IN
(GY)
DIAG
OUT
(PK)
Fr
eigabe
WA
(WH)
DIAG
OUT
(BK)
0
V
DC
(BU)
0
V
DC
(BU)
OSSD
1(
GN)
OSSD
2
(YE)
+2
4
V
DC
(BN)
+2
4
V
DC
(BN)
Brücke 1
Brücke 2
Erdung
E 1
Nur
für
Diagnose
1
2
3
4
DIAG IN (WH)
DIAG OUT
(BK)
Only for Diagnostic
DIAG IN (GY)
Bridge 1
DIAG OUT
(PK)
+24 VDC (BN)
0 VDC (BU)
Release/restart
interlock
(WH)
Bridge 2
+24 VDC (BN)
Contactor control/EDM (RD)
OSSD 2 (YE)
OSSD 1 (GN)
0 VDC (BU)
Earth connection
Restart interlock (manual reset) (bridge 1)
By bridging DIAG IN (pin 5) and DIAG OUT (pin 6), the restart interlock
(manual reset) is activated
Protective mode (bridge 2)
By bridging DIAG OUT (pin 6) and enable (pin 1), the automatic
protective mode is activated Do not connect S1
K1, K2:
Relay for processing the switching outputs
OSSD 1,OSSD 2
Kn1, Kn2: Auxiliary contacts of the last switching relay (optional)
signals at input EDM (pin 8): only to be connected when
the function is activated
S1:
Command device for restart (optional)
E1:
Power supply 24 VDC +/-10%
For proper functioning, the operating mode restart interlock
or operating mode automatic is to be wired
Upon delivery, the "contactor control" function is deactivated
The function is activated by means of the NSR0801 BUS
converter and the PC software