schmersal SLC 420 IP 69 K Operating Instructions Manual Download Page 13

13

EN

SLC 420 IP 69 K

Operating instructions

Safety light curtain

Receiver

LED

Status LED

Description

OSSD ON

On

Protection field clear

flashing

Diagnostic mode active

OSSD OFF

On

Protection field interrupted, system or configuration error

flashing

Diagnostic mode active, error output refer to Fault diagnostic table

Restart

On

Start or restart interlock (manual reset) active, signal expected at output WA

Signal reception

ON/flashing

Signal reception too low, check alignment and installation height between transmitter and receiver
Cleaning the black profile cover

OFF

Alignment between transmitter and receiver OK

Blanking

1 flash

Fixed blanking of the protection field(s)

2 flash

Floating blanking, max 1 beam

3 flash

Variable blanking, more beams

4 flash

Floating (max 1 beam) and fixed blanking of protection field(s)

5 flash

Variable (multiple beams) and fixed blanking of protection field(s)

Multifunction

flashing

Beam coding A is active

Transmitter

LED

Status LED

Description

Transmitting

On

Standard operation, transmitter active

flashing

Configuration error

Status

flashing

Beam coding A is active

6.2  Fault diagnostic

The light curtain performs an internal self-test after the operating voltage is switched on and the protection field is enabled When a fault is detected, 

a corresponding flashing pattern is emitted at the receiver through the LED OSSD OFF (red) Every fault emission is followed by a one-second 

pause

LED OSSD OFF

Fault feature

Action

OSSD OFF and LED restart 
continuous flashing

Wiring error for function selection
(Restart interlock (manual reset), automatic 
mode)

Check connection at the receiver, bridge 1 or
bridge 2 must be wired (refer to Wiring)

1 flash

Error at sensor receiver

Replace receiver

2 flash

Error contactor control OFF

Check connections at contactor control input, refer to
Wiring, check wiring of the auxiliary contacts

3 flash

Error contactor control ON

Check wiring at contactor control input, short-circuit at +UB and 
mass Power reset after fault rectification

4 flash

Errors at the OSSD outputs

Check the wiring of the outputs, OSSD for short-circuit at +UB and 
mass

5 flash

Error configuration data

Check components in case of cascading, check configuration settings 
by means of the NSR-0801 BUS converter

6 flash

Error blanking

The receiver has detected blanked beams as beams without inter-
ruption, ie locking Check the configuration settings by means of the 
NSR-0801 BUS converter, repeat the teach process with blanking

6.3  Extended diagnostic

By means of the optional SLC 420 configuration software and the 

NSR-0801 BUS converter, an extended diagnostic can be executed 

The software provides the status information of the component and 

can represent the individual light lines This feature enables an optimal 

adjustment of the light curtain The diagnostic mode is signalled by the 

OSSD ON and OSSD OFF LED‘s at the receiver In diagnostic mode, 

protective mode is disabled, the ODDS outputs being locked The 

change from diagnostic mode to protective mode is automatically real-

ised after Power Reset, when the BUS converter is no longer integrated 

and the connecting cable of the sensor is reconnected

Summary of Contents for SLC 420 IP 69 K

Page 1: ...instructions are developed to execute safety related functions as part of an entire plant or machine It is the responsibility of the manufacturer of a machine or plant to ensure the correct functional...

Page 2: ...s result ing from the use of unauthorised spare parts or accessories For safety reasons invasive work on the device as well as arbitrary re pairs conversions and modifications to the device are strict...

Page 3: ...olution 14 mm 0 3 10 0 m resolution 30 mm Response time 1 48 L 10 ms 49 144 L 20 ms without beam coding A 1 48 L 15 ms 49 144 L 27 ms with beam coding A Rated operating voltage 24 VDC 10 PELV supply u...

Page 4: ...as Factory setting The SLC 420 system features many functions without additional devices The following table gives an overview of the possible functions and the factory settings configuration Function...

Page 5: ...ombination of fixed and variable blanking is possible This function allows for an interruption of the protection height without the outputs being disabled in case of material movement in the protec ti...

Page 6: ...iver from foreign beams The beam coding A must be set for each sensor receiver and transmitter individually The function is activated by means of the NSR 0801 BUS converter and a PC or laptop If adjac...

Page 7: ...y guard Approach speed Resolution of the safety light curtain Safety light curtain SLC 420 The safety distance for resolutions 14 mm up to 40 mm is calculated by means of the following formula 1 S 200...

Page 8: ...13855 and EN ISO 13857 3 4 1 Minimum distance to reflecting surfaces During the installation the effects of reflecting surfaces must be taken into account In case of an incorrect installation interru...

Page 9: ...0 587 635 671 SLC 420 E R0570 xx 69 RFB 570 667 715 751 SLC 420 E R0650 xx 69 RFB 650 747 795 831 SLC 420 E R0730 xx 69 RFB 730 827 875 911 SLC 420 E R0810 xx 69 RFB 810 907 955 991 SLC 420 E R0890 xx...

Page 10: ...RD 24 VDC BN 0 VDC BU OSSD 1 GN OSSD 2 YE Earth connection Restart interlock manual reset bridge 1 By bridging DIAG IN pin 5 and DIAG OUT pin 6 the restart interlock manual reset is activated Protecti...

Page 11: ...r times 6 Power OFF 7 Remove cable bridges PIN 2 3 4 and if necessary cable bridge PIN 5 6 8 Wire OSSD 1 2 pin 3 4 9 Power ON To reverse the EDM function repeat the procedure step 2 7 If the programmi...

Page 12: ...nery parts can only be accessed by passing through the protection field of the SLC 4 The staff remains within the detection area when works are con ducted on hazardous machinery parts 5 The safety dis...

Page 13: ...D restart continuous flashing Wiring error for function selection Restart interlock manual reset automatic mode Check connection at the receiver bridge 1 or bridge 2 must be wired refer to Wiring 1 fl...

Page 14: ...accordance with the national prescriptions and legislations 8 Appendix 8 1 Contact Consultancy Sales K A Schmersal GmbH Industrielle Sicherheitsschaltsysteme M ddinghofe 30 D 42279 Wuppertal Tel 49 0...

Page 15: ...rson authorized for the compilation of the technical documentation Ulrich Loss M ddinghofe 30 42279 Wuppertal Notified body for the prototype test T V Nord Cert GmbH Langemarckstr 20 45141 Essen ID n...

Page 16: ...Safety Control GmbH Am Industriepark 33 D 84453 M hldorf Inn Telefon 49 0 86 31 187 9 60 Telefax 49 0 86 31 187 9 61 E Mail info safetycontrol com...

Reviews: