schmersal PROTECT SELECT Operating Instructions Manual Download Page 9

9

PROTECT SELECT

PROTECT SELECT OEM

Operating instructions

Multifunctional safety controller

EN

6.  Set-up and maintenance

The person putting into operation for the first time makes the necessary 

settings on the safety module using the setting instructions and then 

verifies these. The following sequence is to be observed.

1. Make settings in accordance with the setting instructions.

2. Compare the read-back displays with the setting instructions.

3. Enter the parameter program CRC in the setting instructions.

4.  Perform acceptance check (checking of function, correct wiring, 

polarity of the actors, …. ).

5. Sign setting instructions and minutes of the acceptance check.

6.  Add setting instructions and minutes of the acceptance check to the 

machine documentation.

6.1  Operating the safety module

The safety module is operated using the rocker switch. If an entry us 

emphasised by a coloured bar (cursor), the menu can be navigated 

by moving the switch up and down. The current entry is selected by 

pressing on it. If this is a parameter, the value can now be set (”up/

down“). The value is similarly accepted by pressing the rocker switch. 

If you actuate “up” the first time you enter a menu, you will reach the 

higher ranking menu. If the screen saver appears (a moving circle), this 

is similarly left by pressing the rocker switch. The term ENTER used in 

the further description for pressing the rocker switch.

6.2  Putting into operation for the first time

1.   After switching on the start screen appears.

SCHMERSAL

PROTECT

SELECT

2.    The request is then made to select the menu 

language (default: English).

Language

English

3.    The necessity for a configuration / parameter 

setting is displayed after ENTER.

4.    Confirm by ENTER.

CAUTION!

Module needs to be 

configured first!

5.    To conduct the configuration a PIN must be en-

tered (factory default: 0000). The entry is made 
number by number using the rocker switch (up/
down). The next number is reached by ENTER.

Enter PIN

0 0 0 0

6.   After correct entry the “Safety module configura-

tion“ screen appears.

Configuration

Safety module

7.    Enter the menu by ENTER. Now select the 

desired program and confirm with ENTER.

Prog 01

Prog 02

Prog 03

Prog 04

Program select

8.   The list of the MSP codes now appears for the 

input circuits. Set the corresponding code for 
every MSP in accordance with the list. After 
entry a plain text display of the selected settings 
appears. ENTER moves back to the code list 
display. If you navigate “up“ with the last MSP 
code, the next menu appears.

  MSP 01:   1 A 5

  MSP 02:   3 6 8

  MSP 03:   6 D 2

  

1 E 7

Input circuit code

MSP 03: (1 E 7)

E-Stop 2K

NC/NC start

Feedback circuit

Start-up + Cycl. Test

9.   If a guard lock is used the selection of the type 

will appear (Power to unlock: Yes/no).

Solenoid interlock

 Power to unlock

10.   Now set the requisite values for the analogue 

inputs and times.

Parameter

Analog inputs

Inputs

Times

11.   Once all settings have been made leave the 

menu by moving "Up" until the query "Save Yes/
No" appears. Confirm with "Yes". All parameters 
are then shown on several screen pages (red 
background). All parameters are marked with 
"M" (modified). Check all values once more and 
scroll further with "ENTER".

12.   After display of “Readback completed“ you will 

reach the PIN entry.

Save Config?

YES

NO

13.   First enter the factory set PIN 0000.

Enter PIN

0 0 0 0

14.   Then you must enter and repeat the new PIN 

from the settings instructions.

Enter new PIN

3 1 0 7

15.   The CRC which is now shown must be entered 

in the settings instructions.

New CRC

Par-CRC: A5778EDB

Write down CRC!

Press button to 

restart...

6.3  Configuration

The setting is made essentially as described in chapter 5.7.

Alternatively:

If the logo appears after switching on, the display of the set program 

is first reached by pressing the rocker switch and then the main menu. 

If no logo appears, but an SPS message, moving “Up” until you reach 

the main menu. Select “Configuration“ here. The PIN to be entered is 

now the one on the settings instructions. The sequence corresponds to 

than of “Putting into operation for the first time”. For the final parameter 

display with red background only altered values marked with a blue “M“ 

are shown and must be checked specially.

LED RUN

lights up: 

operating mode

blinking: 

 Configuration mode or module has the factory 

defaults (see initial parameterization)

6.4  Behaviour in the case of faults

In the event of a fault the following procedure is recommended

1.  UB LED dark: Check voltage supply

2.  ERR LED lights up/flashes: Analyse error message on the display 

and arrange for appropriate actions.

3.  ERR LED dark: Fault cannot be diagnosed by  PROTECT SELECT.  

Action: Check the external cabling

LED ERR

illuminated:  There is a fault (safe condition)

blinking: 

 There is a caution or warning  

(Operation with possible limitations)

Fault/Warnings/Messages appear on the display in plain text.

Summary of Contents for PROTECT SELECT

Page 1: ...neral information for electrical connection 4 4 2 Power supply 4 4 3 Start level 4 4 4 Sensor level 4 4 5 Actuator level 5 5 Operating principle and settings 5 1 Connection operating elements 6 5 2 De...

Page 2: ...se If used incorrectly or not for the intended purpose or in the case of tampering danger to persons or damage to machine and system parts from using the safety module cannot be ruled out 1 7 Exclusio...

Page 3: ...t change Sinusoidal max 2 8 Hz max 50 mA s Input resistance 10 k Safe analogue inputs Category PL SIL CL Single channel If a cable break dominates Cat 3 PL d SIL CL 2 Dual channel Cat 4 PL e SIL CL 3...

Page 4: ...d pins Electrical power cables must be routed separately from communication lines 3 2 Disassembly Unlock the bottom of the enclosure by means of a slotted screwdriver push up and hang out slightly til...

Page 5: ...onductor outputs Q2 Q3 with 24 VDC 2 x safe relay outputs QR1 QR2 with common supply QR0 up to 250 VAC or 24 VDC 4 x operational optional message outputs Y0 Y 3 with 24 VDC Relay outputs 250 V 24V GND...

Page 6: ...y outputs Operational outputs signalling output Clock outputs for the supply of safe digital inputs for short circuit recognition 5 3 Start level Alternatively auto start or manual start falling edge...

Page 7: ...processor MSP which is parameter assigned by a three digit hexadecimal number The 1 position describes the sensor the 2 position the additional function and the 3 position the contact properties The e...

Page 8: ...ing locked guard interlocks Power to lock For solenoid locked guard interlocks The interlock type always applies to all connected guard interlocks Analog inputs Dual Sensor 2 channel analysis of AI0 a...

Page 9: ...the list After entry a plain text display of the selected settings appears ENTER moves back to the code list display If you navigate up with the last MSP code the next menu appears MSP 01 1 A 5 MSP 0...

Page 10: ...leshooting Description of possible error cause and rectification measures Restart Trigger of a new start once the error has been eliminated Configuration Enter PIN Entry of the PIN codes so as be able...

Page 11: ...essary Sensors and emergency stop command devices can be reset in any order Sensor level Safe analogue inputs Implemented in the following application programs for both analogue secure inputs are the...

Page 12: ...ital inputs I00 I01 Operating mode selector switch automatic I00 HIGH I01 LOW manual I00 LOW I01 HIGH I02 I03 Enabling switches MSP 6 Default value 0 0 0 I04 I05 1 sensor MSP 2 Default value 0 0 0 I06...

Page 13: ...ayed Signalling output Y3 error message status indication Manual mode Flashing with 2Hz Warning Flashing with 1Hz Error messages Lights up Safe semi conductor outputs Q0 Q0N Stop 0 or Stop 1 All semic...

Page 14: ...lay outputs QR1 QR2 Stop 0 or Stop 1 All relay outputs are linked to a safe timer Timer Off Delay Stop 0 Timer 0 seconds Default value Stop 1 Timer should be actively adjusted to 0 seconds Application...

Page 15: ...4 sensor MSP 5 Default value 0 0 0 I10 I11 5 sensor MSP 6 Default value 0 0 0 I12 I13 Feedback circuit I14 I15 START RESET or latch interlock for I16 I17 I16 I17 Emergency stop command device MSP 1 De...

Page 16: ...00 Monitoring time for MSP 5 T11 10 00 Monitoring time for MSP 6 T12 10 00 Stable time for MSP 1 E Stop T13 0 10 Stable time for MSP 2 T14 0 10 Stable time for MSP 3 T15 0 10 Stable time for MSP 4 T1...

Page 17: ...conductor outputs are linked to a safe timer Timer Off Delay Stop 0 Timer 0 seconds Default value Stop 1 Timer should be actively adjusted to 0 seconds Safe relay outputs QR1 QR2 Stop 0 or Stop 1 All...

Page 18: ...The muting monitoring time continues The muting lamp Y0 remains on The muting outputs remain set e The workpiece releases the light barrier AOPD The muting monitoring time continues The muting lamp Y0...

Page 19: ...art the safety monitoring the high signal is absent at the corresponding input which means the feedback loop of the integrated actuator is not closed Timeout Disturbed safety switch The time lag betwe...

Page 20: ...56 12103 Berlin ID n 0035 Person authorized for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal P...