Operating voltage, maximum
26.4 VDC
Note (Power supply, general)
stabilised PELV power supply
No-load supply current I
0
, maximum
100 mA
Current consumption with magnet ON, average
200 mA
Current consumption with magnet ON, peak
350 mA / 200 ms
Required rated short-circuit current to EN 60947-5-1
100 A
External wire and device fuse rating
2 A gG
Switching frequency, maximum
0.5 Hz
Electrical data - Magnet control
Designation, Magnet control
IN
Switching thresholds
-3 V … 5 V (Low)
15 V … 30 V (High)
Current consumption at 24V
10 mA
Magnet switch-on time
100 %
Test pulse duration, maximum
5 ms
Test pulse interval, minimum
40 ms
Classification ZVEI CB24I, Sink
C0
Classification ZVEI CB24I, Source
C1
C2
C3
Electrical data - Safety digital inputs
Designation, Safety inputs
X1 and X2
Switching thresholds
−3 V … 5 V (Low)
15 V … 30 V (High)
Current consumption at 24V
5 mA
Test pulse duration, maximum
1 ms
Test pulse interval, minimum
100 ms
Classification ZVEI CB24I, Sink
C1
Classification ZVEI CB24I, Source
C1
C2
C3
Electrical data - Safety digital outputs
Designation, Safety outputs
Y1 and Y2
Design of control elements
short-circuit proof, p-type
Voltage drop U
d
, maximum
2 V