AD-400 /AD-401 Networked Wireless Lock User Guide
TEST LOCK OPERATION
If you encounter problems while performing any of the following tests, review the installation
instructions and this guide and correct any problems.
Mechanical Test
1. Rotate the inside lever. Operation should be smooth, and the latch should retract.
2. Insert the key into the keyway and rotate the key, or the key and lever to open the door. Operation
should be smooth, and the latch should retract.
Electronic Test
Test the AD-400/AD-401 in Factory Default Mode
1. For locks with a keypad, press any number key. The lock should beep.
2. Press the Schlage button. The keypad should light blue for a few seconds.
3. For locks with a card reader, present a credential to the reader. The lock will beep and the left
side of the Schlage button will blink red one time. When the lock is in Factory Default mode, no
credentials are accepted and the lock will respond with one red blink indicating the lock is not
linked with the PIM400.
4. The AD-400/AD-401 has no default PIN or Programming code. The mechanical key must be
used until the AD-400/AD-401 is in Construction Access Mode, or until the AD-400/AD-401 is
communicating with a PIM400 and an access control panel.
Test the AD-400/AD-401 in Construction Access Mode
1. When the Master Construction Credential is presented, the AD-400/AD-401 will beep and the
Schlage button will light green for 20 seconds awaiting the presentation of another credential to
be granted Construction user access.
2. When a valid Construction Access user credential is presented, the lock will unlock for the re-latch
delay period (default three seconds), and the left side of the Schlage button will blink green. When
the lock re-locks after the re-latch delay period, the left side of the Schlage button will blink red.
3. If an invalid Construction Access user credential is presented, the lock will beep and the left side
of the Schlage button will blink red one time. See
Construction Access Mode
on page 6 for more
information.
!
NOTE: Construction Access mode is cancelled when the lock is either linked to a PIM400,
or reset to factory defaults. When Construction Access mode is cancelled, the Master
Construction Credential and all other credentials added using the Master Construction
Credential will no longer function.
Test with the AD-400/AD-401 linked to the PIM400 and Access Control Panel (ACP)
Once the AD-400/AD-401 is linked to the PIM400, the SUS will indicate a successful link.
The SUS will display AD-400/AD-401 operations and communication status with the PIM400.
1. In the SUS “Diagnostics” menu display for the PIM400, choose “Select Door” and set a door
number for the lock being tested. The SUS will display operation and status for: link, reader data,
motor, tamper, battery, request-to-enter, request-to-exit and door position switch.
If the SUS Diagnostics “UNLOCK ON READ” box is checked, all credentials will unlock the
AD-400/AD-401 during diagnostics check.
2. Present a valid credential to the AD-400/AD-401. The Schlage button will blink green, a beep will
sound and the door will unlock for the preset lock delay period. The lock will re-lock after the lock
delay period and the Schlage button will then blink red.
3. If an invalid credential is presented, the Schlage button will blink red, a beep will sound and the
door will not unlock. Credential data for all credentials is reported to the PIM400 and displayed at
the ACP.