Contactors CPP series – Installation and Maintenance Manual
7.3 Checks
After the installation, perform the following checks:
X
Check that the contactors are correctly installed
on the mounting plate or at the base plate of the
main contactor and tightly screwed in place.
X
Check that the main circuit cables are correctly in-
stalled and fit tightly at the main contacts.
X
For DC versions, check that the correct polarity of
the main circuit connection is observed.
X
Check that the control wires of the coil terminals
are correctly installed.
X
Check that the control wires are correctly connect-
ed to the auxiliary switches.
Check the correct assignment and function of the
auxiliary switch using a continuity tester.
X
Switch the contactor several times without acti-
vating the main power circuit.
X
Check the pull-in and drop-off voltage based on
the Schaltbau specifications. See
C45 catalogue
.
X
Check the routing of the wiring. Wires must not be
squeezed or bent. If applicable bundle and secure
wires using cable ties.
X
After every installation or after maintenance,
check the contactor for correct operation in accor-
dance with the following standards:
-
EN/IEC 60077-2
-
EN/IEC 60947-4-1