Maintenance
Contactors CPP series – Installation and Maintenance Manual
Removing the arc chamber
Prior to the following tests/checks, the arc chamber
must be removed from the housing of the contactor.
-
Checking the main contacts for wear (both station-
ary contacts and moving contact bridge)
-
Checking the arc chamber for wear
X
Press the latching lever (1) sideways slightly away
from the contactor and keep it in this position.
X
Remove the arc chamber (2) upwards from the
housing.
1
2
3
Fig. 17: Removing the arc chamber (stand-alone versions)
1
2
3
Fig. 18: Removing the arc chamber unit (built-in versions)
Inserting the arc chamber
(Refer to
Fig. 17 and Fig. 18
)
X
Press the latching lever (1) sideways slightly away
from the contactor and keep it in this position.
X
Insert the arc chamber (2) into the housing.
X
Release the latching lever (1) so that the small pin
(3) on the housing slides into the hole on the latch-
ing lever (1).
X
Make sure that the arch chamber is latched se-
curely.