Schalk UMS 5 Manual Download Page 9

www.schalk.de 

 

Motor controllers

M

ot

or

 c

on

tr

ol

le

rs

System Design: Limit Switches

In combination with UMS 5 or UMS U5 open/close controller

Local controllers

Each UMS 5 controls a drive through outputs 14 and 24.

It is actuated by signals on the local inputs (VA and VZ) from 

conventional double push-buttons. Travel direction interlo-

cking and run time limiting are ensured by the UMS 5.

 

Group and central controllers

Several UMS 5 units can be grouped together by simply 

connecting their auxiliary inputs (NA and NZ) in parallel. They 

can be actuated jointly by connecting another (higher-level) 

controller ahead of them. This creates a 

group

.

Group controllers can in turn be grouped together in the 

same way and actuated jointly by a higher-level controller. 

This further grouping is called 

central control

.

Rain, wind and light

The various limit switches are connected to the VA/VZ or NA/

NZ inputs of the central controller.

Safety-related actuation signals

 for rain or wind 

must be 

connected to the auxiliary inputs as continuous signals

. This 

ensures that the system is locked out for optimal protection 

against user errors.

Actuation signals not related to safety

, such as automatic 

shading or twilight operation, 

are connected to the local 

inputs as momentary pulse signals

.

In this case the system remains fully under control of the 

user.

Local controllers

The individual local controllers are ac-
tuated by the group controller and their 
own push-buttons

Group controllers 

are actuated by the central controller 
and push-buttons 

Central controller

The central controller is actuated by 
sensors and associated limit switches

Limit switches

for rain, light or wind

Summary of Contents for UMS 5

Page 1: ...lications Roller shutters and louvre blinds shutters skylights smoke extraction hoods in fire protection systems door drives valve drives etc Operation The UMS is actuated by standard push buttons wit...

Page 2: ...green Mode setting Mode This sets the operating mode M Motor control short button press for Open Close or Stop J Louvre blind control short button press for fine adjustment of louvre angle or stop lon...

Page 3: ...UMS 5 230V AC UMS U5 230V AC The UMS 5 230V AC model supports the assignment of different phases for the supply voltage the local inputs and auxiliary inputs Attention For UMS U5 supply voltage and c...

Page 4: ...istance 8mm Electrical isolation creepage clearance distance 8mm Central or group control 2 button control Open Close Universal voltage 12 230V AC DC UMS 5 24V UC The 24V UC variant UMS504 and the 12...

Page 5: ...running times the limit switches of some motors may be reached while other motors are still running The motors that are already switched off would then receive inductive voltage at the counterwinding...

Page 6: ...al control 2 button control 1 button control Further local controllers Close Open Central Close Open Group 1 Close Open Local 1 Open Close Local 2 Close Open Group 2 Close Open Local 3 Open Close Loca...

Page 7: ...p control Local control 2 button control 1 button control Open Group 1 Local 1 Local 2 Close Open Close Open Close Open Close Further local controllers Further local controllers Open Close Open Close...

Page 8: ...matic operation Central control Local control 2 button control 1 button control Further local controllers Wind monitor rain monitor or time switch Local 1 Close Open Open Close Local 2 Local 3 Close O...

Page 9: ...higher level controller This further grouping is called central control Rain wind and light The various limit switches are connected to the VA VZ or NA NZ inputs of the central controller Safety relat...

Page 10: ...ening or closing may be necessary depending on the application Light sensor SL 2 Rain sensor SR 1 Wind sensor SW 4 Close Open Central Close Open Local Close Open Local Close Open Local Observe polarit...

Page 11: ...are level controlled in respon se to short press of button and edge controlled when button held down Set louver blind counter run counter running tg is triggered by timeout of VZ or by manual stop Op...

Page 12: ...0 V 50 60 Hz 10 respectively 24 V DC AC 10 Control voltage operating voltage Only UMS 5P NA NZ inputs are 12 230V UC capable Power consumption passive 0 2W active 0 4W Run time 3 240s Automatic closin...

Reviews: