NBS – Fan coil unit 

TECHNICAL DOCUMENTATION 

Installation 

Construction subject to change. 
No return possible. 

Version: 06.05.21 | Page 21 

INSTALLATION 

NBS-100 

The ceiling installation of NBS-100 is executed by means of 
installed fixing lugs.

 

 

NBS-150 

The ceiling installation of NBS-150 is executed by means of a 
pole brace or an equivalent system.

 

 

NOTE 

SCHAKO recommends installing vibration-damping fixing 
elements to avoid structure-borne noise transmission. 

NOTE 

The rods, screws or vibration damping fixing elements 
required for installation are not included in the delivery. 

Minimum distance to obstacles L>300 mm

Minimum distance to obstacles L>400 mm

Condensate drain Ø16 mm 

Condensate drain Ø16 mm 

Check whether the condensate pan is completely emptied by 

partly filling it.

Check whether the condensate pan is completely emptied by 

partly filling it.

Summary of Contents for NBS Series

Page 1: ...274 W 1300 W Q 7 21 kW 16 04 kW QT 9 63 kW 22 15 kW QS 7 04 kW 16 60 kW Heating tW1 45 C tW2 40 C tR 20 C Cooling tW1 7 C tW2 12 C tR 27 C HR 47 Technical data for the standard model according to EU 2...

Page 2: ...ts 5 Air filter 6 Flange 7 Position of the hydraulic connections 8 Droplet separator 9 Mixing unit 9 Flexible connections 10 Supply air and return air boxes 11 Silencer 17 Accessories 18 Installation...

Page 3: ...apacity from 1 2 kW to 11 9 kW Filtering efficiency ISO Coarse 50 As per compliance with eco design requirements NBS 150 Fan group 1 2 or 3 motorised fans Motor 3 speeds Volumetric flow from 883 to 46...

Page 4: ...efficiency ISO Coarse 50 according to ISO 16890 Synthetic filter medium in galvanised steel frame STANDARD MODEL PRODUCT NBS 150 1 Housing Aluminium profiles Galvanised sheet steel with a thickness o...

Page 5: ...150 56 13 24 0 3 39 1 69 100 3 1660 75 17 29 5 5 04 2 55 Housing empty heat exchanger motorised fan air filter SYSTEM WATER REGISTER VERSION R2 2 pipe register 2 pipe rows cooling or heating R4 2 pipe...

Page 6: ...SCHAKO offers a divided filter Classification C5 ISO Coarse 50 standard C6 ISO Coarse 60 for type 150 only NOTE C5 und C6 correspond to efficiencies G3 and G4 to EN 779 invalid Filter removal 1 in ai...

Page 7: ...standard FZ with supply air flange FA with return air flange FB with supply air and return air flange NOTE The screws required for installation of the flexible connection will be delivered together w...

Page 8: ...low direction on the right NOTE The electric connections are fitted on the opposite side of the hydraulic connections Installation W1 W2 NOTE Register thread to EN 10226 standard Heating Pipe male thr...

Page 9: ...d and heat insulation The mixing unit allows the air to be replenished by introducing a fresh air portion M0 without mixing unit standard M1 with mixing unit in air flow direction on the left M2 with...

Page 10: ...290 mm for supply air A1 150 mm for return air A2 150 mm for return air NOTE To connect the flexible connections to NBS the NBS must be configured with a flange NOTE The screws required for installati...

Page 11: ...galvanised sheet steel and are lined with sound and heat insulation The following insulations are possible I0 Without insulation standard I1 Thermal insulation made of polyethylene 10 mm in thickness...

Page 12: ...connection L1x with x spigots DN123 L2x with x spigots DN158 L3x with x spigots DN198 L4x with x spigots DN248 For the number of spigots see table Connection in air flow direction on the right R00 wit...

Page 13: ...ruction subject to change No return possible Version 06 05 21 Page 13 Dimensions with connection open NBS 100 Model B mm B1 mm Number of bores X 100 1 762 290 10 100 2 1232 350 12 100 3 1742 312 16 NB...

Page 14: ...struction subject to change No return possible Version 06 05 21 Page 14 Connecting flange dimensions NBS 100 Model B mm B1 mm Number of bores X 100 1 762 290 10 100 2 1232 350 12 100 3 1742 312 16 NBS...

Page 15: ...ct to change No return possible Version 06 05 21 Page 15 Spigot dimensions NBS 100 Model B mm B1 mm Number of bores X 100 1 762 290 10 100 2 1232 350 12 100 3 1742 312 16 NBS 150 Model B mm B1 mm Numb...

Page 16: ...ct to change No return possible Version 06 05 21 Page 16 Spigot dimensions NBS 100 Model B mm B1 mm Number of bores X 100 1 762 290 10 100 2 1232 350 12 100 3 1742 312 16 NBS 150 Model B mm B1 mm Numb...

Page 17: ...ile ensuring minimum pressure loss NOTE The technical data of the ZMWS NBS can be found directly in the MWS documentation or SCHAKO s selection programme NOTE In cooling mode silencers have to be insu...

Page 18: ...0 65 370 VC03 VPP46 15L0 2 15 2 5 G 30 200 VC04 VPP46 15L0 6 15 2 5 G 100 575 VC05 VPP46 20F1 4 20 4 5 G 1 200 1190 5 0 220 1330 VC06 VPP46 25F1 8 25 4 5 G 1 238 1530 5 0 260 1670 5 5 280 1800 VC07 VP...

Page 19: ...20 0 65 2 50 20 0 65 2 50 V629 VWG41 20 1 00 2 50 20 1 00 2 50 V630 VWG41 20 1 60 2 50 20 1 60 2 50 V631 VWG41 20 1 60 3 45 20 1 60 3 45 V632 VWG41 20 2 50 3 45 20 2 50 3 45 V633 VWG41 20 2 50 4 25 2...

Page 20: ...Dimensions Operation 1 Operating mode selection button back to normal operation 2 Button to set time and switching times of the timer RDG T only 3 Fan operation selection button OK 4 Rotary knob to se...

Page 21: ...quivalent system NOTE SCHAKO recommends installing vibration damping fixing elements to avoid structure borne noise transmission NOTE The rods screws or vibration damping fixing elements required for...

Page 22: ...r you should check to ensure that there are neither corrosion nor leaks and the condensate drains should be cleaned Motorised fan Twice a year the fan operation should be checked in the different spee...

Page 23: ...le Version 06 05 21 Page 23 CIRCUIT DIAGRAMS NBS 100 1 NBS 100 2 NBS 100 3 20 C air temperature range 40 C 20 C air temperature range 40 C 20 C air temperature range 40 C NOTE Type NBS 100 is delivere...

Page 24: ...oil unit TECHNICAL DOCUMENTATION Circuit diagrams Construction subject to change No return possible Version 06 05 21 Page 24 NBS 150 1 NBS 150 2 20 C air temperature range 40 C 20 C air temperature ra...

Page 25: ...ions Model 100 1 100 2 100 3 150 1 150 2 150 3 Supply voltage 230 V AC 50 60 Hz single phase 230 V AC 50 Hz single phase Type of insulation Type B Type B Type of motor 5 speeds 3 speeds Type of protec...

Page 26: ...5 583 130 115 3 86 2 89 665 11 4 11 8 1 4 2 83 484 16 0 34 5 4 522 130 102 3 56 2 64 612 9 8 11 5 1 3 2 61 446 13 8 34 9 3 463 130 91 3 25 2 39 560 8 3 11 2 1 2 2 39 408 11 7 35 4 2 400 130 83 2 90 2...

Page 27: ...6 89 5 06 1186 14 4 11 4 2 6 4 91 838 12 7 34 8 4 874 130 175 6 26 4 56 1077 12 1 11 0 2 5 4 47 763 10 7 35 3 3 752 130 154 5 56 4 02 958 9 8 10 6 2 2 3 99 681 8 7 35 8 2 610 130 139 4 69 3 36 808 7...

Page 28: ...59 11 5 11 2 3 8 7 21 1232 15 1 35 8 4 1305 135 250 9 34 6 81 1607 10 9 11 0 3 7 7 00 1196 14 3 36 0 3 1222 135 231 8 87 6 44 1527 9 9 10 9 3 5 6 67 1139 13 1 36 3 2 1152 135 216 8 47 6 13 1458 9 1 10...

Page 29: ...63 1101 21 7 11 0 2 6 4 49 766 11 9 35 2 se max 3 1450 260 582 9 21 6 92 1586 42 2 12 4 3 3 6 40 1093 22 9 33 2 2 1327 260 489 8 66 6 45 1491 37 7 12 1 3 2 6 02 1028 20 4 33 5 1 1245 260 442 8 27 6 13...

Page 30: ...1582 12 5 10 4 3 8 6 56 1120 9 7 36 1 se max 3 1960 270 921 13 25 9 79 2282 24 3 11 7 5 0 9 34 1595 18 6 34 2 2 1845 270 781 12 68 9 33 2183 22 4 11 5 4 9 8 94 1527 17 2 34 5 1 1719 270 703 12 03 8 80...

Page 31: ...43 17 6 10 8 5 7 10 51 1795 15 6 36 2 se max 3 3529 225 1300 22 15 16 70 3813 39 8 12 5 7 9 16 04 2740 34 1 33 6 2 3330 225 1112 21 27 15 96 3663 37 0 12 3 7 7 15 43 2635 31 7 33 8 1 3169 225 996 20 5...

Page 32: ...52 66 3 55 53 56 61 57 53 50 46 62 2 52 50 53 58 53 49 45 40 58 1 50 48 52 56 49 44 39 34 55 NBS 100 3 5 61 59 65 68 66 63 60 57 71 4 59 57 62 65 63 60 57 53 68 3 57 55 60 62 60 56 53 49 65 2 55 53 57...

Page 33: ...loss in the heat exchanger ps Pa Available static pressure Q kW Thermal capacity QS kW Sensible capacity QT kW Total capacity tL2 C Air outlet temperature tR C Room air temperature tW1 C Water inlet...

Page 34: ...m water register version R2 2 pipe register 2 pipe rows heating or cooling R4 2 pipe register 4 pipe rows cooling or heating L4 4 pipe register 4 and 2 pipe rows cooling and heating 5 Air filter C5 ai...

Page 35: ...red Any special model not included in the order code must be queried before ordering if no details are given processing is impossible EXAMPLE FA NBS 100 1 Z1 Flexible connection for room air condition...

Page 36: ...xxxx length xxxx mm from 0300 to 1000 always with 4 digits in mm 0500 length 500 mm standard 7 Insulation I0 without insulation standard I1 thermal insulation of 10 mm I2 sound and thermal insulation...

Page 37: ...baffles ORDER DETAILS 1 Type ZMWS Accessories for baffle silencer MWS 2 Family NBS for room air conditioning module NBS 3 Model 100 for product NBS 100 150 for product NBS 150 4 Size 1 Size 1 2 Size 2...

Page 38: ...y special model not included in the order code must be queried before ordering if no details are given processing is impossible EXAMPLE LWZ VC03 Accessories for air water systems products Pressure ind...

Page 39: ...egister version 2 pipe register 2 pipe rows heating or cooling R2 2 pipe register 4 rows of pipes cooling or heating R4 4 pipe register 4 and 2 rows of pipes cooling and heating L4 Air filter Air filt...

Page 40: ...n air flow direction on the left L3x connection with x spigot DN248 in air flow direction on the left L4x Connection in air flow direction on the right connection closed in air flow direction on the r...

Page 41: ...0 65 V602 VWG41 10 0 25 1 00 V603 VWG41 10 0 40 0 65 V604 VWG41 10 0 40 1 00 V605 VWG41 10 0 40 1 30 V606 VWG41 10 0 40 1 60 V607 VWG41 10 0 65 1 00 V608 VWG41 10 0 65 1 30 V609 VWG41 10 0 65 1 60 V61...

Reviews: