NBS – Fan coil unit
TECHNICAL DOCUMENTATION
Technical data
Construction subject to change.
No return possible.
Version: 06.05.21 | Page 26
TECHNICAL DATA
NBS-100-1-L4-C5
v
motor
V
L
p
s
W
Q
T
Q
S
V
W
Δp
W
t
L2
V
K
Q
V
W
Δp
W
t
L2
(m³/h)
(Pa)
(W)
(kW)
(kW)
(l/h)
(kPa)
(°C)
(l/h)
(kW)
(l/h)
(kPa)
(°C)
p
s, max
5
337
150
95
2.52
1.82
434
5.2
10.4
1.0
1.87
319
7.5
36.6
4
315
150
84
2.39
1.72
411
4.7
10.3
1.0
1.77
303
6.8
36.8
3
281
150
77
2.17
1.55
373
4.0
10.0
0.9
1.62
276
5.8
37.2
2
242
150
69
1.91
1.36
328
3.1
9.8
0.8
1.43
245
4.6
37.7
1
200
150
64
1.61
1.15
278
2.3
9.5
0.7
1.22
209
3.5
38.2
η
se, max
5
583
130
115
3.86
2.89
665
11.4
11.8
1.4
2.83
484
16.0
34.5
4
522
130
102
3.56
2.64
612
9.8
11.5
1.3
2.61
446
13.8
34.9
3
463
130
91
3.25
2.39
560
8.3
11.2
1.2
2.39
408
11.7
35.4
2
400
130
83
2.90
2.11
499
6.7
10.8
1.1
2.14
365
9.6
35.9
1
331
130
75
2.49
1.80
429
5.1
10.4
1.0
1.85
315
7.3
36.6
V
L, max
5
1002
25
159
5.59
4.40
963
22.6
13.6
1.7
4.13
705
31.6
32.3
4
959
23
151
5.44
4.26
936
21.4
13.4
1.7
4.01
684
30.0
32.5
3
875
19
147
5.12
3.97
882
19.2
13.1
1.7
3.77
643
26.8
32.8
2
773
15
140
4.71
3.61
812
16.5
12.7
1.6
3.46
591
23.0
33.4
1
650
11
133
4.18
3.15
719
13.2
12.2
1.5
3.06
523
18.4
34.1
Heating (2 pipe rows)
: t
W1
= 45 °C, t
W2
= 40 °C, t
R
= 20 °C
Cooling (4 pipe rows)
: t
W1
= 7 °C, t
W2
= 12 °C, t
R
= 27 °C, HR = 47 %
Available static pressure values with clean filter.