Fire damper BSK-RPR-EU 

  

Technical 

documentation 

 Models

 and dimensions 

Construction subject to change 

 

No return possible 

Version: 2015-02-01 | Document: 09/48 | Page 5 

Damper blade projecting ends 

BSK-RPR-EU-S 

 

 

Figure 6: Damper blade projecting ends BSK-RPR-EU-S 

Nominal 

øD 

Operating side (BS) 

Non-operating side (NBS)

size 

[mm] 

L = 455 / 580 

L=455 

L=580

100 98  256 

107 

232

125 123  244 

95 

220

140 138  236 

87 

212

160 158  226 

77 

202

180 178  216 

67 

192

200 198  206 

57 

182

224 222  194 

45 * 

170

250 248  181 

32 * 

157

280 278  166 

17 * 

142

315 313  149 

0 * 

125

355 353  129 

20 * 

Y1 

105

400 398  106 

43 * 

82

450 448  81 

68 * 

57

500 498  56 

93 * 

32 *

* Extension piece 

(on site)

 necessary 

Table 3: Damper blade projecting ends BSK-RPR-EU-S

 

"a" = 50 mm: Minimum distance between the front edge of 
the open damper blade and the finishing protective grating 
(ASG-RF/-RS). 
 
 

Use 

The fire damper type BSK-RPR-EU can be installed as shown 
in the following table. 

Table 4: Usability

 

 

BSK-RPR-EU-F 

 

 

Figure 7: Damper blade projecting ends BSK-RPR-EU-F 

Nominal

øD

Operating side (BS) 

Non-operating side (NBS)

size

[mm]

L = 375 / 500 

L=375 

L=500

100

98

216

67 

192

125

123

204

55 180

140

138

196

47 * 

172

160

158

186

37 * 

162

180

178

176

27 * 

152

200

198

166

17 * 

142

224

222

154

5 * 

130

250

248

141

8 * 

Y1 

117

280

278

126

23 * 

102

315

313

109

40 * 

85

355

353

89

60 * 

65

400

398

66

83 * 

42 *

450

448

41 *

108 * 

17 *

500

498

16 *

133 * 

8 *

Y1

* Extension piece (VT-RF) necessary 

Table 5: Damper blade projecting ends BSK-RPR-EU-F 

 

Instal-

lation 

Use Model/Material 

Mini-
mum 

thick-

ness 

[mm] 

Minimum distance 

between two BSK-

RPR-EU is 

 [mm] 

Fire resistance 

class 

WALL 

solid    appa-

rent density   

 450 kg/m³ 

in 

for example, concrete, masonry according 
to EN 1996 or DIN 1053; solid plaster wall 
boards according to EN 12859 or DIN 18163

150 200 

EI120 

(v

e

 i

o) S 

Summary of Contents for BSK-RPR-EU Series

Page 1: ...ances or p data es ch urn actuators rts on texts ranch offices ures tables di chad KG 10 drive s n projecting end agrams ds 1 1 1 1 1 1 2 2 Te Fa ww 1 3 6 7 7 8 10 10 11 13 15 17 21 23 Install elephon...

Page 2: ...tumescent seals Horizontal position of the damper blade axle The installation position is independent of the air flow direction Thermal trigger via fusible link 72 C optionally at an extra charge with...

Page 3: ...urn possible Version 2015 02 01 Document 09 48 Page 3 MODELS AND DIMENSIONS BSK RPR EU S plug in connection Figure 1 Dimensions BSK RPR EU S BSK RPR EU F flanged connection Figure 2 Dimensions BSK RPR...

Page 4: ...PR EU S is delivered by default with a rubber lip seal Figure 3 Rubber lip seal Trigger device thermomechanical Figure 4 Trigger device BSK RPR EU Flange bores BSK RPR EU F Figure 5 Flange bores Table...

Page 5: ...de and the finishing protective grating ASG RF RS Use The fire damper type BSK RPR EU can be installed as shown in the following table Table 4 Usability BSK RPR EU F Figure 7 Damper blade projecting e...

Page 6: ...e dampers before and after mounting and ensure ready access Electrical installations or work on electrical components may only be carried out by skilled electricians The supp ly voltage must be switch...

Page 7: ...des with ventila tion ducts BK Fire damper BSK RPR EU ASG Finishing protective grating type ASG 1 VT Extension piece type VT LL Ventilation duct SW Shaft wall SR Closing direction LR Air flow directio...

Page 8: ...to 250 Nominal sizes 250 to 500 Diagram 1 Pressure loss and flow generated noise without finishing protective grating Application limits max operating pressure of 1000 Pa at vstirn 10 m s Pressure los...

Page 9: ...00 98 2 44 2 74 2 49 2 80 125 123 2 83 3 21 2 89 3 29 140 138 3 06 3 49 3 13 3 57 160 158 3 35 3 84 3 43 3 93 180 178 3 65 4 20 3 74 4 31 200 198 3 97 4 59 4 07 4 70 224 222 4 37 5 07 4 48 5 19 250 24...

Page 10: ...ignalling and switching bus system type EasyBus Fire damper mini controller BKSYS Extension piece type VT RF 1 Assembly part type REBT 2 required for installation of the smoke detection system type RM...

Page 11: ...upply voltage in accordance with regula tions and unlocked mechanically Display of the damper end positions is possible by me ans of integrated micro switches via potential free changeover contacts co...

Page 12: ...position W 0 8 1 1 Power consumption dimensioning 4 VA Imax 8 3 A 5 ms 6 5 VA Imax 4 A 5 ms Auxiliary switch 2 x EPU Switching capacity of auxiliary switch 1 mA 3 0 5 inductive A AC 250 V Connection...

Page 13: ...2 on page 4 Nominal size D mm L mm The dimension L depends on the nominal size 100 98 160 125 123 140 138 160 158 180 178 200 198 224 222 250 248 280 278 315 313 355 353 400 398 450 448 500 498 190 T...

Page 14: ...248 280 278 315 313 355 353 400 398 450 448 500 498 Table 10 Dimensions REBT Figure 18 Round duct assembly type REBT side view front view and top view Position indicator type MSZ Figure 19 Position in...

Page 15: ...1 V2A Housing with DD coating solvent containing two component top coat based on polyurethane var nish RAL 7035 light grey inside outside Housing with powder coating RAL 9010 pure white inside and out...

Page 16: ...charge for anticorrosive paint inside and outside DD coating two component top coat based on polyurethane varnish RAL 7035 light grey Extra charge for powder coating RAL 9010 pure white inside and out...

Page 17: ...e of the damper blade and of the manual lever There is a risk of in jury The fire damper must close and lock automatically locking of the damper blade in the closed positi on 1 3 Opening the fire damp...

Page 18: ...pply Fire damper must close automatically locking is performed by blocking the spring return actuator 2 3 Replacement of the thermoelectric release device if necessary Exchange takes place by unscrewi...

Page 19: ...no Series Release device The following function steps have been carried out according to the documents installation mounting and operating instructions Prior to com missioning Next functional test in...

Page 20: ...chako de Web www schako de Sample Functional test protocol for fire dampers Cons No ____________________ Defects found during the test on ________________________________________ Sluggishness due to s...

Page 21: ...02 51620946 Fax 385 51 701 470 info europersis gr insupco netvision net il info schako it ri intel trade hr www europersis gr www insupco com www schako it www intel trade hr Luxembourg Niederlande st...

Page 22: ...00 Praha 10 Zabehlice San ve Tic Ltd Sti Tel 421 337 741 843 Calle B nave 3 Tel 42 02 727 680 43 Pursaklar Sanayi Sitesi Fax 421 337 741 843 E 50840 San Mateo de G llego Fax 42 02 727 693 93 Karaca re...

Page 23: ...ng return actuator 11 Figure 15 Connecting diagram B10 B11 11 Figure 16 Extension piece type VT RF 13 Figure 17 Finishing protective grating type ASG RS RF 13 Figure 18 Round duct assembly type REBT s...

Reviews: