Caution 
Supply Voltage 
Condition 

Do not power the MT-8000/6000 and inductive DC loads

, or input 

circuitry to the controller, with the same power supply. Note: The 24 VDC 
output from some controllers may not have enough current to power the 
MT-8000/6000. 

 

Caution  
Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 
1000’ (300 m) unshielded). 
Wires should be run in pairs with a neutral or common paired with a hot or 
signal line. 
If wiring is to be exposed to lightning or surges, use appropriate surge 
suppression devices. 
Keep AC, high energy, and rapidly switching DC wiring separate from 
signal wires. 
Equip ungrounded DC supplies with a resistor and capacitor in parallel to 
earth ground. This provides a path for static and high frequency dissipation. 
Typical values to use are 1MOhm and 4700pF. 

 

Caution  
 

To prevent the HMI from becoming damaged or having sound output issues, 
after turning the device off, please wait 10 seconds before turning the device 
on again. 

 

Connection 

To make a connection, strip about 3/8” of insulation off the end of the wire, 
turn the connector screw counterclockwise until the gap is wide open, insert 
the wire all the way in, and turn the screw clockwise until it’s tight. 
Connect positive DC line to the ‘+24V’ terminal and the DC ground to the 
‘0V‘ terminal. 

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 
ground internally. It is preferable not to ground DC negative return to chassis 
ground as poor site earths can introduce noise into a system, but if necessary 
an earth connection should be made, from the power supply return point to 
the central star earth point. Ground conductors should be as short and as large 
in size as possible. The conductors must always be large enough to carry the 
maximum short circuit current of the path being considered. Ground 
conductors should be connected to a tree from a central star earth ground 
point. This ensures that no ground conductor carries current from any other 
branch. 

 

 

 

2.2.3 CE Requirements 

To make an MT-8000/6000 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 

power connector. This ground connection should be run directly to the central star earth connection 

point (as recommended in most Installation Instructions). 

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

 

3

 

Hardware 
Considerations 

WARNING! 
The system designer should be aware that devices in Controller systems could 
fail and thereby create an unsafe condition. Furthermore, electrical 
interference in an operator interface, such as an MT-8000/6000, can lead to 
equipment start-up, which could result in property damage and/or physical 
injury to the equipment operator. 
If you, or your company, use any programmable control systems that require 
an operator or attendant, you should be aware that this potential safety hazard 
exists and take appropriate precautions. Although the specific design steps 
depend on your particular application, the following precautions generally 

Summary of Contents for MT-8000 Series

Page 1: ...00 Series has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire routing and grounding will insure proper operation Mechanical Environment Avoid installing units in environments where severe mechanical vibration or shocks are present 2 0 Installatio...

Page 2: ...e gases vapors or dusts z The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device z Do not install these terminals in environments where have inflammable gases 2 2 Power Connections Make sure that all local and national electrical standards are met when the installing the unit Contact your local authori...

Page 3: ...noise into a system but if necessary an earth connection should be made from the power supply return point to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough to carry the maximum short circuit current of the path being considered Ground conductors should be connected to a tree from a central star earth gr...

Page 4: ...nded as safeguards against the failure of critical components and the effects of such failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation z The ICS 3 304 81 Safety Recommendations are reproduced by permission of the National Electrical Manufacturers Association from NEMA ICS 3 304 2 3 Communications Connections The ports as you lo...

Page 5: ... RS 232 Port Pin Symbol Com1 RS485 2w Com1 RS485 4w Com3 RS485 Com3 RS232 1 Rx Data Rx 2 Rx Data Rx 3 Tx Tx 4 Tx Tx 5 GND Signal Ground 6 Data Data 7 TxD Transmit 8 RxD Receive 9 Data Data 2 3 3 USB Host port 5 Support various devices with USB interface such as mouse keyboard USB stick printer etc 2 3 4 Connecter Wire MT8 Ethernet RZC045120 Direct connect Ethernet crossover cable MT 8000 6000 Ethe...

Page 6: ...re at Flash Rom z If losing or forgetting system passwords users can set Dip Switch 1 to ON position the rest of Dips remain on OFF position and then reboot MT 8000 6000 Under this situation MT 8000 6000 will jump to Touch Adjust Touch screen calibration mode After calibration the pop up window appears as the illustration below Users will be inquired if restoring the system password to the default...

Page 7: ...lass A Radiated Emissions levels EN50081 2 Generic emission standard industrial environment Also US FCC Class A EN50082 2 Generic immunity standard industrial environment 3 0 Specifications MT6070T MT8070T Hardware Specification Display 7 TFT LCD Brightness 350 cd m2 Color 65 536 colors Contrast Ratio 200 1 Resolution WxH dots 480 x 234 Back light LED CCFL life time avg 30 000 hr min Touch panel 4...

Page 8: ...wiring current leakage from machine platform and incorrect input power c if the product has been maintained in a manner not conforming to product s instructions or has been modified in any way d if the serial number has been defaced or removed 4 0 Dimensions of MT 6070T MT 8070T Cutout dimensions MT 8070T 192mm 7 559 W x 138mm 5 433 H Bottom View a DIP SW Reset button e USB Host x 2 b Fuse f Com1 ...

Reviews: