2.1.2 Making a NEMA-4 Mounting 

Panel  
Details

 

The unit can be mounted into panels with a depth of 4”(105mm).    It is recommended that 
the unit be mounted on the front panel of a steel enclosure, through an appropriate 
opening*. Allow a clearance of 1”(25mm) around the sides of the unit for mounting 
hardware. Allow clearance for cable connections to the back of the unit. Unit depth may 
vary according to cable type used. Typically, plan a depth to accommodate at least 
4”(105mm) behind the panel. 

NEMA-4 
Mounting

 

Put the unit through the panel cut out. Slide the clamps into the 6~8 holes provided around 
the case. Tighten the clamping screws in an even pattern until the unit is secured in the 
panel. 

Caution!

 

Do not over tighten mounting clamps! 

Note:

 

Specifications 

Note: To seal to NEMA-4 specifications, all supplied mounting clamps must be used and 
panel cannot flex more than 0.010”. 

2.1.3 Environmental Considerations 

 

z

 

The MT-8000/6000 are to be used indoors as built in displays. Make sure that the 
displays are installed correctly and that the operating limits are followed (See 
Specifications). 

z

 

Do not operate the unit in areas subject to explosion hazards due to flammable gases, 
vapors or dusts. 

z

 

The unit should not be installed where fast temperature variations and/or high humidity 
are present. This will cause condensation of water in the device. 

z

 

Do not install these terminals in environments where have inflammable gases. 

 

 

2.2 Power Connections 

Make sure that all local and national electrical standards are met when the installing the unit. 
Contact your local authorities to determine which codes apply. 

2.2.1 Power Requirements 

 

 

Power

 

The MT-8000/6000 can be powered by DC power only. The specified 
voltage range is 

24±10%

 Volts DC. This insures compatibility with most 

controller DC systems.   
The power conditioning circuitry inside the unit is accomplished by a 
switching power supply. The peak starting current can be as high as 700mA.

 

Fusing 
Requirements

 

If the display does not come on within 2 seconds of power up, remove 
power. An internal fuse will prevent damage if the polarity of the DC power 
is incorrect. Check wiring to insure proper connections and try to power up 
again. 

 

Caution 
High Voltage

 

An Internal fuse will prevent damage for over voltage condition however it 
isn’t guaranteed. 
DC voltage sources should provide proper isolation from main AC power 
and similar hazards. 

 

Caution 
Emergency 
Stop

 

A Hard-wired EMERGENCY STOP should be fitted in any system using an 
MT-8000/6000 to comply with ICS Safety Recommendations. 

2

 

Summary of Contents for MT-8000 Series

Page 1: ...00 Series has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire routing and grounding will insure proper operation Mechanical Environment Avoid installing units in environments where severe mechanical vibration or shocks are present 2 0 Installatio...

Page 2: ...e gases vapors or dusts z The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device z Do not install these terminals in environments where have inflammable gases 2 2 Power Connections Make sure that all local and national electrical standards are met when the installing the unit Contact your local authori...

Page 3: ...noise into a system but if necessary an earth connection should be made from the power supply return point to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough to carry the maximum short circuit current of the path being considered Ground conductors should be connected to a tree from a central star earth gr...

Page 4: ...nded as safeguards against the failure of critical components and the effects of such failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation z The ICS 3 304 81 Safety Recommendations are reproduced by permission of the National Electrical Manufacturers Association from NEMA ICS 3 304 2 3 Communications Connections The ports as you lo...

Page 5: ... RS 232 Port Pin Symbol Com1 RS485 2w Com1 RS485 4w Com3 RS485 Com3 RS232 1 Rx Data Rx 2 Rx Data Rx 3 Tx Tx 4 Tx Tx 5 GND Signal Ground 6 Data Data 7 TxD Transmit 8 RxD Receive 9 Data Data 2 3 3 USB Host port 5 Support various devices with USB interface such as mouse keyboard USB stick printer etc 2 3 4 Connecter Wire MT8 Ethernet RZC045120 Direct connect Ethernet crossover cable MT 8000 6000 Ethe...

Page 6: ...re at Flash Rom z If losing or forgetting system passwords users can set Dip Switch 1 to ON position the rest of Dips remain on OFF position and then reboot MT 8000 6000 Under this situation MT 8000 6000 will jump to Touch Adjust Touch screen calibration mode After calibration the pop up window appears as the illustration below Users will be inquired if restoring the system password to the default...

Page 7: ...lass A Radiated Emissions levels EN50081 2 Generic emission standard industrial environment Also US FCC Class A EN50082 2 Generic immunity standard industrial environment 3 0 Specifications MT6070T MT8070T Hardware Specification Display 7 TFT LCD Brightness 350 cd m2 Color 65 536 colors Contrast Ratio 200 1 Resolution WxH dots 480 x 234 Back light LED CCFL life time avg 30 000 hr min Touch panel 4...

Page 8: ...wiring current leakage from machine platform and incorrect input power c if the product has been maintained in a manner not conforming to product s instructions or has been modified in any way d if the serial number has been defaced or removed 4 0 Dimensions of MT 6070T MT 8070T Cutout dimensions MT 8070T 192mm 7 559 W x 138mm 5 433 H Bottom View a DIP SW Reset button e USB Host x 2 b Fuse f Com1 ...