Vent Installation Procedure

This appliance must be vented through dual 3 inch 

flexible gas aluminum liners listed for use with gas 

appliances.  

The co-linear installation includes a pair of 3 inch 

flex ducts that run from the insert up through the 

existing chimney.

One duct is attached to the exhaust port on the 

back of the unit and will carry the exhaust gases to the 

outside of the house. This exhaust liner must run the 

full length of the chimney and be directly connected to 

the chimney termination cap.  See figure 8.

The other 3 inch liner will be attached to the air in-

take port on the back of the unit and will provide fresh 

air for combustion to the unit.  This liner must extend a 

minimum of 6 feet off the back of the unit  and extend 

through the damper area of the fireplace and into the 

tile liner of the chimney. This liner can also extend the 

full length of the chimney and connect to the termina-

tion cap.  See figures 8 and 9.

         

IMPORTANT

If the intake flex does not extend the full length 

of the chimney and connect to the unit and the 

termination cap -  A METAL BLOCK OFF PLATE MUST 

BE CONSTRUCTED AND INSTALLED ABOVE THE UNIT 

BELOW THE END OF THE INTAKE DUCT (normally at 

the damper area).  See figure 8.

To avoid cross venting the insert, label the duct to 

be used for the exhaust conduit at both the top and 

bottom ends. This ensures that the exhaust duct will 

be attached to the correct collar on the insert and on 

the chimney termination kit.

CANADA NOTE:  Both Intake and Exhaust ducts 

must extend the full length of the chimney and be 

connected to both the unit and the termination kit.

IMPORTANT NOTICE:
THE USE OF AN EXISTING CHIMNEY AS AN AIR 

INTAKE IS NOT COVERED UNDER THE ANSI Z21.88-

1999-CSA 2.33-M99 TEST METHODS AND RESULTING 

ITS/WHI PRODUCT CERTIFICATION.  THE CODE 

AUTHORITY HAVING JURISDICTION MUST BE 

CONSULTED PRIOR TO PROCEEDING WITH THIS 

INSTALLATION METHOD.

Vent Guidelines

•  All vent components must be installed in accordance 

with the terms of their listing and manufacturer’s 

instructions.

•  The minimum height of termination cap from the 

top of the unit shall be no less than 10’, and the maxi-

mum height shall be no more than 40’.  See figures 2 

and 4.

•  Steep roofs, nearby trees, or predominantly windy 

conditions can promote weak draft or occasional 

downdrafts. In such cases, increasing the height of 

the vent or installation of high wind termination 

caps may alleviate the condition.

•  HORIZONTAL RUNS are not permitted anywhere in 

the venting system.  

•  Venting liners CANNOT be less than 3” in diameter or 

greater than 3” in diameter.

•  Any unused flue or masonry enclosure can be used 

as a passageway for venting PROVIDED the flue is 

relined using 3” Listed Flexible Gas Liner.

•  The remaining space around the liner in a masonry 

or zero-clearance flue CANNOT be used to vent any 

other appliance.

•  Listed Flexible Gas Liners may not be exposed to any 

living space. 

•   Installation of any components not manufactured 

or approved by Scan or failure to meet all clearance 

requirements will void all warranties and could result 

in property damage, bodily injury, or loss of life.

•  Never modify any venting component, or use any 

damaged venting product.

•  THE GAS APPLIANCE AND VENT SYSTEM MUST BE 

VENTED DIRECTLY TO THE OUTSIDE OF THE BUILD-

ING, AND NEVER ATTACHED TO A CHIMNEY SERVING 

A SOLID FUEL OR GAS BURNING APPLIANCE. 

•  The minimum vent height above the roof or adjacent 

walls is specified by building codes. A general guide 

to follow is the Gas Vent Rule below.

  

GAS VENT RULE

Flat to 6/12 

1’0”       0.3M 

Over  7/12 to 9/12 

2’0”      0.6M 

Over 10/12 to 12/12 

4’0”      1.2M 

Over 13/12 to 16/12 

6’0”      1.8M 

Over 17/12 to 21/12  

8’0”      2.4M

 

Minimum Height 

From Roof

ROOF SLOPE

Summary of Contents for 45i

Page 1: ...l Ne touchez aucum interrupteur Ne pas vous servir des t l phones se trou vant dans le b timent o vous trouvez Appelez imm diatement votre fournis seur de gaz depuis un voisin Suivez les instructions...

Page 2: ...ucts be installed and serviced by professionals who are certified in the U S by the National Fireplace Institute NFI as NFI Gas Specialists THIS PRODUCT MUST BE INSTALLED BY A LICENSED MASTER OR JOURN...

Page 3: ...the glass out of the way 5 The Starfire Glass Embers or Tumbled Stone burner media is packaged separately from the insert firebox Figure 1 Pull each Trunk Latch down to disengage it from the Glass Fr...

Page 4: ...an 45i gas fireplace insert has been tested and listed as a direct vent gas fireplace heater and listed to ANSI Z21 88 2009 CSA 2 33 2009 CAN CGA 2 17 M91 and CSA P 4 01 2 for Canada Starfire Glass Em...

Page 5: ...ve been established in CAN CGA B149 Fuel Installation Code Installer l appareil selon les codes ou reglements locaux ou en l absence de tels reglements selon les Codes d installation CAN CGA B149 5 Do...

Page 6: ...ace Never burn any solid materials wood cardboard paper coal etc in this gas fireplace Use with natural gas or propane fuel ONLY Any safety screen glass or guard removed for servicing the appliance mu...

Page 7: ...tallation of the brackets allows the insert to be raised up to 2 1 2 off of the hearth Also note that use of the leveling brackets will affect required minimum clearance to combustible top trim and ma...

Page 8: ...18 forward of the firebox glass panel Raised Hearth A raised hearth that is at least 6 high requires a non combustible hearth that extends a minimum 12 from the fireplace glass and and is a minimum o...

Page 9: ...ment This appliance requires 120 V AC power to operate the blower accent lamps and electronic ignition Four AA batteries provide back up power in case of a power outage Leg Leveler Bolts and Brackets...

Page 10: ...3 M99 TEST METHODS AND RESULTING ITS WHI PRODUCT CERTIFICATION THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD Vent Guidelines All vent compo...

Page 11: ...into the chimney flue and ultimately into the intake duct to the insert 9 Compress the ducts so that they are hanging above the height of the fireplace opening and are out of the way 10 Position the i...

Page 12: ...ESULTING ITS WHI PRODUCT CERTIFICATION THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD Figure 9 Venting through prefabricated fireplace chimn...

Page 13: ...ut holes for both the intake and exhaust liners in the block off plate C A direct vent cap is still required to allow fresh air into the chimney flue and ultimately into the intake flex and insert D A...

Page 14: ...13 85 WC NECESSARY MANIFOLD PRESSURES inches water column MIN MAX NATURAL GAS 1 6 WC 3 5 WC PROPANE 5 3 WC 11 0 WC ALWAYS TEST PRESSURE WITH THE VALVE REGULATOR ADJUSTED TO THE HIGHEST SETTING Figure...

Page 15: ...ilot rectification and or frequent burner outages Little variation in flame picture between HI and LO regulator settings Insufficient gas to support more than one ap pliance causing nuisance outages o...

Page 16: ...BLIS DANS LES IN STRUCTIONS DE PROPRIETAIRE PROVISIONNEES AVEC L EQUIPEMENT Conversion Kit LP 157249 NG 157250 Tools required 1 2 13 mm open end wrench or deep well socket Torx T20 driver 1 4 nut driv...

Page 17: ...ocated it should not be able to move to the right or left 10 Replace the variable regulator on the gas control valve Using a Torx T 20 screwdriver remove the two screws from the regulator tower on the...

Page 18: ...aller and applied to the appli ance at the time of the conversion See fig 19 Derating procedure 1 Turn off gas supply to the appliance and disconnect from electrical power source 2 Remove the Glass Fr...

Page 19: ...ening the air shutter will generate a flame that is blue and transparent or an anemic flame This flame is generally more efficient but not very attractive We recommend the following settings for the S...

Page 20: ...shutter See figs 14 and 15 pages 16 17 4 Use a 10 mm socket to remove the left and right burner bracket nuts Remove the Burner Bracket from the firebox See fig 23 5 Bend the two upper rear tabs down...

Page 21: ...ure 26 Install Glass Embers Tumbled Stones Kit 157245 NOTE Install the optional Reflective Glass Panels before installing the stones Spread the stones evenly around the burner media tray CAUTION Take...

Page 22: ...Figure 28 At the thermostat the two wires should be connected to the two connection screws on the thermostat base plate according to the manufacturer s instructions For the thermostat to function the...

Page 23: ...e Backing Plate or Trimmable Backing Plate See fig 31 Starting at the small precut slot use a straight edge to draw a guideline across the leg Use a disk grinder to cut off the excess material and fil...

Page 24: ...there is no call for heat Ideal for use with thermostatic or remote control this feature ignites the pilot flame only when there is a call for heat A battery back up permits continued use in the event...

Page 25: ...not lifting or float ing The flame should be blue in color around the pilot hood with traces of yellow toward the outer edges It is important that the pilot flame engulf the top 1 8 of the flame recti...

Page 26: ...s and particulate accumulation may appear on the inside surface to the glass Use a dampened soft cloth to clean the glass and polish with a dry soft towel Specially formulated ceramic glass cleaner ma...

Page 27: ...214 Screw 8 X 1 4 Taptite SLHWH SZPL 21 223980 ProflameValve Manual Hi Lo NG 22 223215 Adaptor Straight Brass 3 8 NTP x 3 8 Dia Flare 23 129707 Flex tube w connectors 3 8 O D x 24 24 222280 Gasket Dro...

Page 28: ...Part Number Description 1 117917 Screw HWH SMA 8 x 1 2 SL Blk Oxide 2 222799 Blower Bracket 3 222072 Blower TransFlow 12 Cage 120 CFM No Part Number Description 1 117917 Screw HWH SMA 8 x 1 2 SL Blk...

Page 29: ...rs Simpson Dura Vent Inc P O Box 1510 Vacaville CA 95696 1510 800 835 4429 Selkirk Corporation 1301 W President George Bush Hwy Suite 330 Richardson TX 75080 1139 800 992 8368 American Metal Products...

Page 30: ...osts associated with the repair of gas controls plumbing burners log set or sheet metal firebox beyond the warranty period 5 Damage caused by unauthorized modification use or repair 6 Damage to enamel...

Page 31: ...ouch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone If your gas supplier cannot be reached call the fire department 1 Set the...

Page 32: ...ion it is important that the these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in specification color or ty...

Reviews: