2.8 TIME
Date and time adjustment
DATE
Date
TIME
Time
2.9 INPUT
Mode of operation and limit value adjustments
DISPLAY
Cont
continuous
measurement
Min
min. measured value is displayed and restored by a trigger pulse.
Max
max measured value is displayed and restored by a trigger pulse.
LIMIT
Limit values are active only when mode of operation is selected.
VALUE SETS SP1_1 switch point 1 of (GWS1) switch point and switching direction adjustable.
SP1_2 switch point 1 of (GWS2) switch point and switching direction adjustable.
SP2_1 switch point 2 of (GWS1) switch point and switching direction adjustable.
SP2_2 switch point 2 of (GWS2) switch point and switching direction adjustable.
OPERATION GWS off
all limit values and external tare are switched-off.
MODE
GWS/TARE
GWS 1 and external tare is active.
GWS 1+2
GWS 1 and 2 are active, GWS2 is activated via control input.
3 CALIB
Calibration menu – this is active only, if the password has been entered correctly
in 2.5PASS. For the calibration the sensor needs to be connected to the sensor
socket.
Sensor__
Sensor number or name of the sensor which is to be calibrated.
POINTDIS
Measuring range with decimal indication of the sensor, e.g. 100,0; 200,0; 63,00;...
Call menu "POINTDIS", after pressing
ENTER
the final value of the sensor can be entered, by
PLUS
or
MINUS
the
numeric character can be edited, by
ENTER
the next figure can be edited, if all
figures are edited, by
PLUS
and/or
MINUS
the comma will be shifted. For the completion of the
input press
ENTER,
thereafter the final value is being logged in the GM 80.
UNIT
Input of the physical unit, e.g. Kg, Ncm, t, gr, kN, N·m, bar...
DESIG
Name of the sensor e.g. sensor 1,2,3, silo, tank, mixer, balance1, motor, test1..
CALIB
Selection of the sensor type (active, passive, 4-20mA, with or without calib. control..)