SBS-6000 25
5.3.5
Alarm Threshold Setting
Functions description
Set the alarm & replacement value of the battery resistance. If test
battery’s resistance, the setting value should be the multiple of the
reference value. If test conductance, the setting value should be the
percentage of the reference value.
How to use
Select the alarm threshold setting and enter into the setting display, if
it is resistance testing, the display as follow:
TEST SETTING
2011-05-10 09:01:23
1. String Mode:
7. Sample Test:
2. Cell Mode:
3. Conn Mode:
6. Set Test Type
:
4. Save Mode:
5. Set Warning:
Warning
:
1.5 REF
Fail
:
2.0 REF
8. Zero Setting:
Enter
Esc
+0.1
-0.1
Click up & down keys to select the items you want to set. Click
<+0.1><-0.1> function key to set the alarm and replacement threshold
and then save. The alarm & replacement value should be the multiple
of the reference resistance value. 1.5REF means the instrument will
warning and alarm when the testing results 1.5 times greater and 2
times less than the reference value. 2.0REF means the instrument will
process replacement alarm when the testing value 2 times greater than
the measured value.