Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Overview of room operating devices
Room operating devices
7-3
7
Furthermore, the LEDs on the PCD7.L632, Q.RCU-A-TSO and the LC display of
the PCD7.LR-TR42x can be configured to provide information on the following:
Overriding of the controller, e.g. by pressing the “Occupancy” key on the room
operating device or by receiving a network command via the controller
(see section “LEDs on room operating devices for displaying information on
overrides” below).
Effective occupancy mode of the controller
(see the following section “Configuring the LEDs on room operating devices for
displaying information concerning occupancy”).
Supported functions of Q.RCU-A-txxx
room operating devices
Temp. setting
Setpoint setting
Presence button
Fan speed override
LED
*
Required UI con
-
troller inputs
Q.RCU-A-T
●
─
─
─
─
1
Q.RCU-A-TS
●
●
─
─
─
2
Q.RCU-A-TSO
●
●
●
─
●
2
Q.RCU-A-TSOF
●
●
●
auto-0-1-2-3
●
3
Supported functions of PCD7.L63x room operating
devices
Temp. setting
Setpoint setting
Presence button
Fan speed override
LED
*
Required UI con
-
troller inputs
PCD7.L630
●
─
─
─
─
1
PCD7.L631
●
●
─
─
─
2
PCD7.L632
●
●
●
─
●
2
* An output is additionally needed to operate the LED. Only the PCD7.LRL2-P5 has a
dedicated LED output. Other variants require an AO that can operate at a minimum of 5 mA.