X1 - USB Port (Programming Interface)
Communication ports
12-1
12
12
Communication ports
X6
X2
X1
X7
X5
X4
X9
Terminal
Portnumber
(Software-
adress)
Description
X1
PGU
Programming
X2
Port #2
Port #10
S-Bus, free protocol
Profi S-Net
X4
Port #0
Integrated RS-485
terminal
X5
Port #1
Slot A
interface selectable with
PCD7.F1xxS
X6
Port #9
Dual Ethernet Switch
X7
X9
Port #8
Profibus-DP
with PCD2.F7500
12.1
X1 - USB Port (Programming Interface)
Plug:
Standard vertical USB series B (device plug)
Default:
USB 1.1 device (slave), full speed 12 Mbps,
with Softconnect
Protection: transil
Hardware: On-board USB 5V supply
The USB port is only used as a PGU interface. To use the USB interface,
the program package Saia PG5
®
version 2.0 or later must be installed on the PC.
If the PCD is connected to the PC for the first time through the USB port, the PC
operating system (Windows) automatically loads the corresponding Saia PCD
®
USB driver. To connect the PCD via USB, the following setting is required in the
Saia PG5
®
project folder for the device concerned under “Online settings”:
Activating the “PGU option” ensures
that the PCD connected to the PC can
be reached directly, independently of
the configured S-Bus address.