Saia-Burgess Controls AG
User Manual PCD2.M4x60 │
Document 27-648
│ Edition ENG06 │ 2020-10-21
Usage as interruptive inputs
Interrupts
10-2
10
10.2
Usage as interruptive inputs
Terminal block X8
25
24
23
22
21
20
DI_IX3
DI_IX2
DI_IX1
DI_IX0
terminal block
X8
Source operation
Interrupt-
inputs
To use the digital inputs as interruptive inputs, choose the mode “Interrupt”.
The interrupts can be triggered on rising edge, falling edge or both.
A XOB is called when an interrupt is
detected. The XOB number is config
-
ured by default at XOB 20 for input 0
up to XOB23 for Input 3.
Input
Assigned to
DI_IX0
XOB 20
DI_IX1
XOB 21
DI_IX2
XOB 22
DI_IX3
XOB 23
Device configurator