Assembly and operating instructions AWD3D5WD 

Three-phase active power energy meter with serial Modbus interface, Pic. 1

Description

Energy meter with serial Modbus interface enables the rea-

ding of all relevant data like consumption, current, voltage 

and power (active and reactive).

Indicating elements (Pic. 4)

T1total (kWh) 

 

Shows total consumption

T1part. (kWh) 

  

Shows partial consumption, this 

value is resettable

CT 

  

Shows the set current transformer 

ratio

Select 

  

The transformer ratio can be 

selected in Menu item Select, in 

the open bridge Z1-Z2

P(kW) 

  

Shows the instantaneous power  

per phase or all phases

U(V) 

 

Shows the voltage per phase

I(A) 

 

Shows the current per phase

kWh 

  

Shows the unit kWh when the 

consumption is displayed

L1 / L2 / L3 

  

For P-, U-, I- or Error display, the 

corresponding phase is displayed

Error 

  

In case of missing phase or wrong 

current direction. The correspond-

ing phase is additionally displayed.

Technical data

Connection  

  Pic. 2

diagram

Dimensions 

 

Pic. 3

Accuracy class 

 

B according to EN50470-3,  

 

 1 according to IEC62053-21

Reference, Maxi- 

 

I

ref

 = 5 A, Ima

x =

 6 A, Ist =

 1

0 mA

mum, initial current

operating voltage 

 

3 × 230/400 V

AC

, 50 Hz 

 

  Tolerance −20%/+15%

Counting range 

  000 000,0…9 999 999 kWh

LED-Ouptut  

  10 Imp/kWh 

Connections 

 

Conductor cross-section 1,5−16 mm

2

Main circuit 

  screwdriver pozi no. 1, slot no. 2,  

 

  torque 1,5−2 Nm

Connections 

 

Conductor cross-section max. 2,5 mm

2

,  

Control circuit 

  screwdriver pozi no. 0, slot no. 2,  

 

  torque 0,8 Nm

Operating  

 

−25 … +55°C (noncondensing

temperature 

  according standard EN50470)

Environment  

  Mechanical M2

 

  Electromagnetic E2

Notes before connecting 

1.  Do not connect L1, L2 or L3 to N

2.  In order to avoid moisture in the meter due to condensa-

te build-up, acclimatise the meter at room temperature 

for about half an hour before connecting.

3.  N must always be connected.
Attention!

These devices must only be installed by a professional 

electrician, otherwise there is the risk of fire or the risk of 

an electric shock.

Declaration of Conformity CE

We, Saia-Burgess Controls AG, CH 3280 Murten (Switzer-

land), herewith declare, on our own responsibility that 

the products:

 

 

AWD3D5WD00C3A00

which this certificate refer to, are in accordance with the 

directive 2004/22/EG (MID) and the following standards:
 

  EN50470 parts 1 and 3 (electronic meter), of  

  October 

2006. 

Murten, 30.04.2013

Conformity Assessment Body:

    METAS-Cert, Nr. 1259

  CH-3003 

Bern-Wabern 

Signed: Jean-Paul Costa, Head of development

English

Installation instructions

The three-phase energy meter can be attached to a 35 mm 

rail (EN60715TH35). 

The meter can be used only in installation cabinets. 

Operation of the LCD display

See page with LCD menu navigation.

The bridge Z1-Z2 should be removed for adjusting the 

transformer ratio.

4 319 5114 0b  

09.2013  

Subject to change without notice

Wiring diagram

The secondary, mains current transformer 

connection is to be connected to the phase to 

be measured and therefore the transformer 

don’t have to be grounded. 

This connection is to be fused according to the local 

installation instructions.

Summary of Contents for AWD3D5WD

Page 1: ... 22 7 4 5 11 35 5 x 11 7 58 5 6 4 5 27 31 45 82 69 5 7 68 6 9 Pic 1 Pic 3 Pic 2 Pic 4 CT Select D D CT Select U V T1part P kW T1total Error L3 I A L1 L2 Class B AWD3D5W L1 L2 L3 N l S2 k S1 L P2 K P1 Modbus over RS 485 serial line max 1200 m PEN Fuse min T 250 mA 3x 431951140b 3 230 VAC 400VAC ...

Page 2: ...tsprechende Phase angezeigt Error Bei fehlender Phase oder falscher Stromrichtung Die entsprechende Phase wird zusätzlich angezeigt Hinweise vor dem Anschliessen 1 Nicht die Phase L1 L2 oder L3 an N anschliessen 2 Um Feuchtigkeit im Zähler durch Kondenswasser zu vermeiden den Zähler vor dem Anschliessen ca eine halbe Stunde bei Raumtemperatur akklimatisieren 3 N muss immer angeschlossen sein Achtu...

Page 3: ...ten sollte ein Repeater benutzt werden Die Schnittstelle hat keinen Abschlusswiderstand dieser sollte extern bereitgestellt werden Die verwendeten Register sind in der Registerliste beschrieben Datenübertragung Nur Read Holding Registers 03 Write Multiple Registers 16 Anweisungen werden erkannt Es können bis zu 20 Register auf einmal gelesen werden Das Gerät unterstützt Broadcast Nachrichten Gemäs...

Page 4: ...r double registers 4 5 16 17 28 29 30 31 the high register is sent first big_Endian The Partial counter 30 31 can be reset by writing 0 in both registers in the same message R Typ Description Unit 33 R Not Used Will give 0 34 R Not Used Will give 0 35 R Not Used Will give 0 36 R URMS phase 1 Effective Voltage of Phase 1 V Ex 230 230 V 37 R IRMS phase 1 Effective Current of Phase 1 A Except 5 5 10 ...

Page 5: ... 0 slot no 2 torque 0 8 Nm Operating 25 55 C noncondensing temperature according standard EN50470 Environment Mechanical M2 Electromagnetic E2 Notes before connecting 1 Do not connect L1 L2 or L3 to N 2 In order to avoid moisture in the meter due to condensa te build up acclimatise the meter at room temperature for about half an hour before connecting 3 N must always be connected Attention These d...

Page 6: ...vices a repeater should be used The interface don t have a terminal resistor this should be provided external For a description of the used registers please look at the register page Data transmission Only Read Holding Registers 03 Write Multiple Registers 16 instructions are recognized Up to 20 Registers can be read at a time The device supports broadcast messages In accordance with the Modbus pr...

Page 7: ...al T2part T1total P kW L1 L3 L2 T1 total T1 part Ratio Current Transformer CT Instan Power P 3 s 3 s I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 AWD3D5WS00C_A00 5 1500 A 5 5 50 5 100 5 150 5 200 5 250 5 300 5 400 5 500 5 600 5 750 5 1000 5 1250 5 1500 5 3 s Start 20 s I...

Page 8: ... I o Errore Error In caso di mancanza di una fase o di direzione della corrente sbagliata Viene visualizzata la fase interessata Dichiarazione di conformità CE Noi Saia Burgess Controls AG CH 3280 Murten Svizzera dichiarammo in nostra propria responsabilità che i prodotti AWD3D5WD00C3A00 di quali si riferisce questa dichiarazione rispondono alla direttiva 2004 22 CE MID e alle normative seguente n...

Page 9: ...ipetitore L interfaccia non è provvista di resistenza terminale che quindi dovrà essere messa a disposizione separatamente I registri utilizzati sono descritti nell elenco dei registri Trasmissione dei dati Vengono riconosciute solo le istruzioni Read Holding Registers 03 Write Multiple Registers 16 Possono essere letti fino a 20 registri alla volta L apparecchio supporta messaggi braodcast In bas...

Page 10: ... T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 Voltage U Current I Start I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3...

Page 11: ...ase kWh Indique l unité kWh pour l affi chage de consommation L1 L2 L3 En cas d affichage P U I ou Error la phase correspondante s affiche Error En cas d absence de phase ou de sens de courant inversé La phase correspondante s affiche également Déclaration de conformité CE Nous Saia Burgess Controls AG CH 3280 Murten Suisse déclarons sous notre propre responsabilité que les produits AWD3D5WD00C3A0...

Page 12: ...eils est supérieur à 128 utiliser si possible un répéteur L interface n est pas dotée d une résistance de terminaison celle ci doit être mise en place de façon externe Les registres utilisés sont décrits dans la liste de registres Transfert de données Seules les instructions de type Read Holding Registers 03 Write Multiple Registers 16 sont supportées Jusqu à 20 registres peuvent être lus en même ...

Reviews: