R
Typ Description
Unit
1
R
Firmware-Version
Ex:11 =FW 1.1
2
R
Number of supported
registers
Will give 52
3
R
Number of supported
flags
Will give 0
4–5
R
Baudrate
Ex: Baudrate High = 1 Baudrate
Low = 49664
1 × 65536 + 49664 =
115’200 bps
6
R
Not Used
Will give 0
7
R
Type / ASN function
Will give «AW»
8
R
Type / ASN function
Will give «D3»
9
R
Type / ASN function
Will give «D5»
10
R
Type / ASN function
Will give «FW»
11
R
Type / ASN function
Will give «00»
12
R
Type / ASN function
Will give «Cx»
x : 2 = Non MID
x : 3 = Non MID
13
R
Type / ASN function
Will give «A0 »
14
R
Type / ASN function
Will give «0»
15
R
HW vers. Modif.
Ex: 11 =HW 1.1
16–17
R
Serial number
Unique 32 bit serial number low
18
R
Serial number
Unique 32 bit serial number high
19
R
Not Used
Will give 0
20
R
Not Used
Will give 0
21
R
Not Used
Will give 0
22
R
Status
0 = no Problem
1 = problem with last
communication request
23
R
Response timeout
ms
24
R/W
1)
Modbus Address
Range 1–247
25
R
Error register
0 : No error
1 : Error Phase 1
2 : Error Phase 2
3 : Error Phase 1+2
4 : Error Phase 3
5 : Error Phase 1+3
6 : Error Phase 2+3
7 : Error Phase 1, 2+3
26
R
Current Transformer
Ratio
Ex: Transformer 100 / 5 give 20
27
R
Not Used
Will give 0
28–29
R
WT1 total High
Counter Energy Total
Tariff 1 High
10
–1
kWh (multiplier 0,1)
Ex: WT1 total High = 13
WT1 total Low = 60383
13 × 65536 + 60383 =
912351 = 91235.1 kWh
30–31 R/W WT1 partial
Counter Energy Partial
Tariff 1
10
–1
kWh (multiplier 0,1)
Ex: WT1 partial High = 13
WT1 partial Low = 60383
13 × 65536 + 60383 =
912351 = 91235.1 kWh
32
R
Not Used
Will give 0
Registers
For double registers (4 – 5, 16 – 17, 28 – 29, 30 – 31) the high register is sent first (big_Endian).
The Partial counter (30 – 31) can be reset by writing 0 in both registers in the same message.
R
Typ Description
Unit
33
R
Not Used
Will give 0
34
R
Not Used
Will give 0
35
R
Not Used
Will give 0
36
R
URMS phase 1
Effective Voltage of
Phase 1
V
Ex: 230 = 230 V
37
R
IRMS phase 1
Effective Current of
Phase 1
A / Except 5/5 = 10
–1
A
Ex: 314 = 314 A
38
R
PRMS phase 1
Effective active Power
of Phase 1
10
–1
kW (multiplier 0,1)
Ex: 1545 = 154,5 kW
39
R
QRMS phase 1
Effective reactive Power
of Phase 1
10
–1
kvar (multiplier 0,1)
Ex: 1545 = 154,5 kvar
40
R
cos phi phase 1
10
–2
(multiplier 0,01)
Ex: 67 = 0,67
41
R
URMS phase 2
Effective Voltage of
Phase 2
V
Ex: 230 = 230 V
42
R
IRMS phase 2
Effective Current of
Phase 2
A / Except 5/5 = 10
–1
A
Ex: 314 = 314 A
43
R
PRMS phase 2
Effective active Power
of Phase 2
10
–1
kW (multiplier 0,1)
Ex: 1545 = 154,5 kW
44
R
QRMS phase 2
Effective reactive Power
of Phase 2
10
–1
kvar (multiplier 0,1)
Ex: 1545 = 154,5 kvar
45
R
cos phi phase 2
10
–2
(multiplier 0,01)
Ex: 67 = 0,67
46
R
URMS phase 3
Effective Voltage of
Phase 3
V
Ex: 230 = 230 V
47
R
IRMS phase 3
Effective Current of
Phase 3
A / Except 5/5 = 10
–1
A
Ex: 314 = 314 A
48
R
PRMS phase 3
Effective active Power
of Phase 3
10
–1
kW (multiplier 0,1)
Ex: 1545 = 154,5 kW
49
R
QRMS phase 3
Effective reactive Power
of Phase 3
10
–1
kvar (multiplier 0,1)
Ex: 1545 = 154,5 kvar
50
R
cos phi phase 3
10
–2
(multiplier 0,01)
Ex: 67 = 0,67
51
R
PRMS total
Effective active Power of
all phases
10
–1
kW (multiplier 0,1)
Ex: 1545 = 15,45 kW
52
R
QRMS total
Effective reactive power
of all phases
10
–1
kvar (multiplier 0,1)
Ex: 1545 = 15,45 kvar
1)
The Modbus Address register is not writable with a broadcast message.