Technical data Modbus

Bus system 

 

Modbus, RTU according to IDA specification

Transmission rate 

1200-2400-4800-9600-19 200-38 400-57 600-115 200.

     

 

The transmission Baud rate is automatically detected

Transmission mode  

 Even parity: 8 data bits, 1 stop bit 

Odd parity: 8 data bits, 1 stop bit 

No parity: 8 data bits, 2 stop bits

Bus length (max.) 

1200 m (without repeater)

Response time:   

Write: 60 ms

     

 

Read: 60 ms

 

The Interface works only if the phase 1 is connected.

 

The communication is ready 30s after the power on

 

The use of energy meter in Bus with intensive communication could reduce the performance of the Bus

 

Refresh time for the data is 10 s. For this reason one energy meter should be not polled faster as 10s. 

 

247 devices could be connected to the Modbus. Over 128 devices, a repeater should be used.

 

The interface don’t have a terminal resistor, this should be provided external.

 

For a description of the used registers please look at the register page

Data transmission

 

Only «Read Holding Registers [03]/ Write Multiple Registers [16]» instructions are recognized.

 

Up to 20 Registers can be read at a time.

 

The device supports broadcast messages.

 

In accordance with the Modbus protocol, a register R is numbered as R - 1 when transmitted.

 

The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM (transmission rate, etc.)

Exception Responses

  ILLEGAL FUNCTION [01]: The function code is not supported.

  ILLEGAL DATA ADDRESS [02]: The address of some requested registers is out of range  

or more than 20 registers have been requested.

  ILLEGAL DATA VALUE [03]: The value in the data field is invalid for the referenced register.

Change the Modbus address direct on device

 

To modify the Modbus address, press 3 s on 

 touch

 

In menu, 

 increase address by 10, 

 increase by 1

 

Once the address is selected wait for the root menu to come back

English

Summary of Contents for AWD3D5WD

Page 1: ... 22 7 4 5 11 35 5 x 11 7 58 5 6 4 5 27 31 45 82 69 5 7 68 6 9 Pic 1 Pic 3 Pic 2 Pic 4 CT Select D D CT Select U V T1part P kW T1total Error L3 I A L1 L2 Class B AWD3D5W L1 L2 L3 N l S2 k S1 L P2 K P1 Modbus over RS 485 serial line max 1200 m PEN Fuse min T 250 mA 3x 431951140b 3 230 VAC 400VAC ...

Page 2: ...tsprechende Phase angezeigt Error Bei fehlender Phase oder falscher Stromrichtung Die entsprechende Phase wird zusätzlich angezeigt Hinweise vor dem Anschliessen 1 Nicht die Phase L1 L2 oder L3 an N anschliessen 2 Um Feuchtigkeit im Zähler durch Kondenswasser zu vermeiden den Zähler vor dem Anschliessen ca eine halbe Stunde bei Raumtemperatur akklimatisieren 3 N muss immer angeschlossen sein Achtu...

Page 3: ...ten sollte ein Repeater benutzt werden Die Schnittstelle hat keinen Abschlusswiderstand dieser sollte extern bereitgestellt werden Die verwendeten Register sind in der Registerliste beschrieben Datenübertragung Nur Read Holding Registers 03 Write Multiple Registers 16 Anweisungen werden erkannt Es können bis zu 20 Register auf einmal gelesen werden Das Gerät unterstützt Broadcast Nachrichten Gemäs...

Page 4: ...r double registers 4 5 16 17 28 29 30 31 the high register is sent first big_Endian The Partial counter 30 31 can be reset by writing 0 in both registers in the same message R Typ Description Unit 33 R Not Used Will give 0 34 R Not Used Will give 0 35 R Not Used Will give 0 36 R URMS phase 1 Effective Voltage of Phase 1 V Ex 230 230 V 37 R IRMS phase 1 Effective Current of Phase 1 A Except 5 5 10 ...

Page 5: ... 0 slot no 2 torque 0 8 Nm Operating 25 55 C noncondensing temperature according standard EN50470 Environment Mechanical M2 Electromagnetic E2 Notes before connecting 1 Do not connect L1 L2 or L3 to N 2 In order to avoid moisture in the meter due to condensa te build up acclimatise the meter at room temperature for about half an hour before connecting 3 N must always be connected Attention These d...

Page 6: ...vices a repeater should be used The interface don t have a terminal resistor this should be provided external For a description of the used registers please look at the register page Data transmission Only Read Holding Registers 03 Write Multiple Registers 16 instructions are recognized Up to 20 Registers can be read at a time The device supports broadcast messages In accordance with the Modbus pr...

Page 7: ...al T2part T1total P kW L1 L3 L2 T1 total T1 part Ratio Current Transformer CT Instan Power P 3 s 3 s I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 AWD3D5WS00C_A00 5 1500 A 5 5 50 5 100 5 150 5 200 5 250 5 300 5 400 5 500 5 600 5 750 5 1000 5 1250 5 1500 5 3 s Start 20 s I...

Page 8: ... I o Errore Error In caso di mancanza di una fase o di direzione della corrente sbagliata Viene visualizzata la fase interessata Dichiarazione di conformità CE Noi Saia Burgess Controls AG CH 3280 Murten Svizzera dichiarammo in nostra propria responsabilità che i prodotti AWD3D5WD00C3A00 di quali si riferisce questa dichiarazione rispondono alla direttiva 2004 22 CE MID e alle normative seguente n...

Page 9: ...ipetitore L interfaccia non è provvista di resistenza terminale che quindi dovrà essere messa a disposizione separatamente I registri utilizzati sono descritti nell elenco dei registri Trasmissione dei dati Vengono riconosciute solo le istruzioni Read Holding Registers 03 Write Multiple Registers 16 Possono essere letti fino a 20 registri alla volta L apparecchio supporta messaggi braodcast In bas...

Page 10: ... T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 Voltage U Current I Start I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3 L2 I A U V Error T1part T2total T2part T1total P kW L1 L3...

Page 11: ...ase kWh Indique l unité kWh pour l affi chage de consommation L1 L2 L3 En cas d affichage P U I ou Error la phase correspondante s affiche Error En cas d absence de phase ou de sens de courant inversé La phase correspondante s affiche également Déclaration de conformité CE Nous Saia Burgess Controls AG CH 3280 Murten Suisse déclarons sous notre propre responsabilité que les produits AWD3D5WD00C3A0...

Page 12: ...eils est supérieur à 128 utiliser si possible un répéteur L interface n est pas dotée d une résistance de terminaison celle ci doit être mise en place de façon externe Les registres utilisés sont décrits dans la liste de registres Transfert de données Seules les instructions de type Read Holding Registers 03 Write Multiple Registers 16 sont supportées Jusqu à 20 registres peuvent être lus en même ...

Reviews: