background image

Assembly and operating instructions Type ALD1D5F10K 

32 A Single Phase active power energy meter with S0 interface, Pic. 1

Description

Energy meter with S0-interface for the integrated 

transmission of measured values in building automation. 

The LC - display add value such as power and read voltage 

and current.

Technical data

Connection  

  Pic. 2

diagram

Dimensions 

 

Pic. 3

Accuracy class 

 

B according to EN50470-3,  

 

 1 according to IEC62053-21

Reference, Maxi- 

 

I

ref

 = 5 A, Im

ax 

= 32 A, Ist

 =

 20 mA

mum, initial current

operating voltage 

 

230 V

AC

, 50 Hz 

 

  Tolerance −20%/+15%

Counting range 

  00 000,00…999 999,9 kWh

S0-Ouptut  

   Optocoupler max. 30V/20mA and 

min. 5V, impedance 100Ω, pulse 

duration 30ms 

1000 Imp./kWh

Connections 

 

Conductor cross-section max. 6 mm

2

,

 

Main circuit 

  screwdriver pozi no. 1, slot no. 1,  

 

  torque 1,2 Nm

Connections 

 

Conductor cross-section max. 2,5 mm

2

,  

Control circuit 

  screwdriver pozi no. 0, slot no. 1,  

 

  torque 0,5 Nm

Operating  

 

−25…+55°C (noncondensing

temperature 

  according standard EN50470)

Environment  

  Mechanical M2

 

  Electromagnetic E2

Notes before connecting 

In order to avoid moisture in the meter due to condensate 

build-up, acclimatise the meter at room temperature for 

about half an hour before connecting.

Attention!

These devices must only be installed by a professional 

electrician, otherwise there is the risk of fire or the risk of 

an electric shock.

Declaration of Conformity CE

We, Saia-Burgess Controls AG, CH 3280 Murten (Switzer-

land), herewith declare, on our own responsibility that 

the products:

 

 

ALD1D5F10KA3A00

 

 

ALD1D5F10KB3A00

which this certificate refer to, are in accordance with the 

directive 2004/22/EG (MID) and the following standards:
 

  EN50470 parts 1 and 3 (electronic meter), of  

  October 

2006. 

ESD on equipment side: 13 kV.

Murten, 30.04.2013

Conformity Assessment Body:

    METAS-Cert, Nr. 1259

  CH-3003 

Bern-Wabern 

Signed: Urs Tanner, Site Quality Leader

English

Installation instructions

The energy meter can be attached to a 35 mm rail 

(EN60715TH35). 

The meter can be used only in installation cabinets. 

Operation of the LCD display

See page with LCD menu navigation. For the versions 

ALD1D5F10KB3A00 and ALD1D5F10KB2A00 (without 

button) there is no menu navigation possible.

4 319 5078 0F  

03.2017  

Subject to change without notice

Indicating elements

Ttotal (kWh) 

 

Shows total consumption 

Tpart. (kWh) 

  

Shows partial consumption, this 

value is resettable

P (kW) 

 

Shows the instantaneous power 

U (V) 

 

Shows the voltage 

I (A) 

 

Shows the current 

2000 Imp/kWh  

  

Pulsates according to drawn power. 

Error indication (line 1L/2L inverted) 

with pulsating 600/600 ms. 