※1 Ambient temp 25℃
※2 Ambient temp 25℃~-16℃
5. TROUBLE SHOOTING
10
Power supply output voltage.
Approx. AC13V - 17V ※1
■ Does not get Cold
(Temperature setting -18℃)
Is compressor
running?
Lower than AC13V
Checking
Is special fuse
blown?
Are wirings and couplers
connected?
A
Power supply is broken.
Replace the
power supply.
Replace the fuse
Check the fridge, Go to A
See page 14
【Check 1】
See page 13
【Check 2】
Test result
Judge
Fixing
Connected repair.
Replace the
power supply.
Replace the
cooling unit.
Resistance of the thermistor.
Approx. 2kΩ - 10kΩ※2
Thermistor is broken.
∞Ω
Replace the
thermistor.
Power supply output voltage.
Approx. AC13V - 17V ※1
AC 0V
Power supply is
broken.
Replace the
power supply.
Lower than AC13V
Output
maladjustment.
See page14
【Check 4】
Output
maladjustment
See page 13
【Check 2】
Normal
Repeats fuse blown.
Yes
Yes
No
No
Yes
Normal
Normal
No
Yes
No
cooling unit
is broken.
Higher than 2.0A
The compressor is locked, or
contaminated.
Lower than 1.5A
Gas is leaking.
Compressor rated current.
Approx. 1.5A - 2.0A
Replace the
cooling unit.
See page 15
【Check 6】
Is temperature
controller (digital
display) lit?
check the teperature controller.
Normal
Abnormal
See page 14
【Check 5】
teperature controller
is broken.
Replace the
teperature
controller
.