61
8-04
Restart after momentary power failure (Mode selection)
Factory setting
d 0
Setting range
d 0
Inactive(Trip immediately)
d 1
Active(Restart at the frequency at which the power failure occurred, for
general loads)
d 2
Active(Restart at the starting frequency, for light inertia loads)
8-05
Restart after momentary power failure(Max allowable time for power
failure)
Factory setting
d 2.0
Setting range
d 0.3<->d 5.0s
Unit
0.1s
This parameter shall set Max allowable time for power loss in case of momentary power loss and if function of
Restart after momentary power failure is started. If power supply breaking time exceeds Max allowable time, output
of AC inverter shall stop after power resupplied.
8-06
Restart after momentary power failure (Restart time)
Factory setting
d 0.5
Setting range
d 0.3<->d 5.0s
Unit
0.1s
If power supply interruption is detected, AC motor drive shall stop output and shall not be re-started until after set
time by this parameter. It’s preferred to provide output side residual voltage to be approximately 0V prior to inverter
starting.When setting external B.B and restart after alarm, this parameter shall be time for speed tracking.
8-07
Restart after momentary power failure
(Max current setting for speed tracking)
Factory setting
d 150
Setting range
d 30<->d 200%
Unit
1%
8-08
Jump frequency 1(Upper)
Factory setting
d 0.0
8-09
Jump frequency 1(Lower)
Factory setting
d 0.0
8-10
Jump frequency 2(Upper)
Factory setting
d 0.0
8-11
Jump frequency 2(Lower)
Factory setting
d 0.0
8-12
Jump frequency 3(Upper)
Factory setting
d 0.0
8-13
Jump frequency 3(Lower)
Factory setting
d 0.0
Setting range
d 0.0<->d 400Hz
Unit
0.1Hz
Parameters above define inhibited frequency setting, and this range shall be avoided from frequency setting for
inverter, reason is that frequency output shall not be stable at these ranges but shall stay beyond these ranges of
frequency. However, since frequency output shall be continuous, when frequency is not set within these ranges,
frequency output shall be continuous and jumping shall not occur at locations of inhibition frequency.
Max allowable time for power failure
8-05
Input power
supply
Max allowable time for power failure
8-05
Track upwards from
speed before power
loss of inverter
= d2
8-04
8-06
Restart time
Speed synchronous detection
Output
frequency
Output
voltage
= d1
8-04
Track downwards
from speed before
power loss of inverter
8-06
Restart time
Speed search