26
4. Input Function Parameters
Set during running available
Paramet
er
Parameter functions
Setting range
Factory
setting
4-00
[VR] Input frequency bias setting
0.0 to 350Hz
0.0
4-01
[VR] Input frequency bias adjustment
direction
0: Positive direction
1: Negative direction
0
4-02
[VR] Input frequency gain setting
1 to 200%
100
4-03
[VR] Negative bias operation setting
0: No negative bias
1: Reversible negative bias
2: not reversible negative bias
0
4-04
Terminal (MI1) function
(Setting range from d0 to d31)*
0: No function
1: MI1: forward run/stop, MI2: reverse run/stop
2: MI1: run/stop, MI2: fwd/rev run
3: 3-line operation control(1): MI1 run, MI2
fwd/rev run, MI3 STOP(Normally closed)
4: 3-line operation control(2): MI1 run
(Triggering) ,MI2 run(Triggering), MI3
STOP(Normally closed)
5: External fault(EF), normally open interface
input (N.O)
6: External fault(EF) normally closed interface
input (N.C)
7: RESET alarm
8: Select multi-frequency (0 to 1 steps)
9: Select multi-frequency (0 to 3 steps)
10: Select multi-frequency (0 to 7 steps)
11: Reserved
12: Select frequency command 2/1
13: Accel /decel inhibition command
14: Select 1
ST
and 2
nd
Accel/Decel time
15: External alarm, normally open (NO) input
16: External alarm, normally closed(NC) input
17: Up command
18: Down command
19: Pattern operation command
20: Pattern operation pause command
21: JOG frequency reference
22: Count reset
23: Reserved
24: JOG-FWD
25: JOG-REV
26: Reserved
27: Wobble frequency function input
28: Wobble frequency state reset
29: Inhibiting output (N.O)
30 :Inhibiting output (N.C)
31: Counter trigger signal input
1
4-05
Terminal (MI2) function
(Setting range d0, d5 to d31)
0
4-06
Terminal (MI3) function
(Setting range d0, d5 to d31)
8
4-07
Terminal (MI4) function 4
Setting range d0, d5 to d31)
9
4-08
Terminal (MI5) function
(Setting range d0, d5 to d31)
7