3. Output Function Parameters
Set during running available
Parame
ter
Parameter functions
Setting range
Factory
setting
3-09
Terminal [MO1] Function
0: No function
1: Inverter running
2: Frequency arrival
3: Zero speed
4: Over-torque detection
5: During external alarm
6. Low voltage detection
7: External terminal running mode
8: Alarm output (for any alarm)
9: Frequency detection
10:During pattern operation
11. Pattern operation one cycle completion
12. Pattern operation completion
13: Pattern operation pause
14:Terminal count value arrival
15: Terminal designated count value arrival
16: Inverter ready to run
17: Fwd running
18: Rev running
19: Fwd/ Rev run direction
1
3-10
Reserved
3-11
Dead time setting of Fwd and Rev
changeover
0.0 to 600 s
0.0
3-12
Cooling fan control
0: Fan continuous running
1: Run for 1 minute after pressing stop key
2: Operate/stop along with inverter
0
3-13
Bias [AVI] (Bias base point)
0.0 to 10.0V
0.0
3-14
Bias [AVI] (Bias value)
0.0 to 100% of Maximum Frequency
0.0
3-15
Analog input Adjustment for [AVI]
(Gain base point)
0.0 to 10.0V
10.0
3-16
Analog input Adjustment for [AVI]
(Gain)
0.0 to 100% of Maximum Frequency
100
3-17
Bias [ACI] (Bias base point)
0.0 to 20.0mA
4.0
3-18
Bias [ACI] (Bias value)
0.0 to 100% of Maximum Frequency
0.0
3-19
Analog input Adjustment for [ACI]
(Gain base point)
0.0 to 20.0mA
20.0
3-20
Analog input Adjustment for [ACI]
(Gain)
0.0 to 100% of Maximum Frequency
100
3-21
reserved
3-22
reserved
Parameters marked with
“reserved” will be displayed, but will not be used for the inverter. Please do not change the
code of such kind of parameter.