42
Set frequency through "
∧
"and "
∨
" on keyboard and UP/DOWN terminals (frequency
setting increase/ decrease) function.They have the highest authority and can combine with
any other frequency setting channel. They mainly adjusts the output frequency of inverter in
the course of debugging control system.
0: Available and the inverter stores after power-failure. Able to set the frequency command
and store the set frequency value after power- failure. It will combine with present setting
frequency automatically when powering on again.
1: Available, the inverter dose store parameters on power-lost. Able to set the frequency
command,but not store the set frequency value after power-failure.
2:UP/DOWN setting unavailable, the function of "
∧
"and "
∨
"on keyboard and UP/DOWN
terminal are unavailable and motor resets automatically.
3:The function setting of "
∧
"and "
∨
"on keyboard and UP/DOWN terminal available on
running.
4
:
Reserved
Note: when user restores the function parameter of inverter, the keyboard and
UP/DOWN function terminal reset automatically.
Select the inverter A frequency command input channel. Seven main set frequency
channels.
0: Keyboard setting
Keyboard sets frequency through modifying the value function code 00-06.
1: Analog quantity AV11 setting (single-phase 220V 0.4~0.75kW corresponds to the
potentiometer on keyboard. And it corresponds to the 485 communication keyboard on
potentiometer if using the 485 communication keyboard externally, while the local
potentiometer ceases to be effectiveness automatically.)
2: Analog quantity AV12 setting
3: Analog quantity AV11+ AV12 / ACI setting
The frequency is set by analog quantity input terminal , S2800 serial inverter standard
configurations provide two-way analog quantity input terminals, AVI1 is 0~10V voltage input
and AV12 / ACI could be 0~10V/0 (4)~20mA. The current and voltage can be switched
through jump wires.
Setting range
0: Keyboard setting
1: Analog quantity AV11 setting
2: Analog quantity AV12 setting
3: AV11+ AV12 / ACI
4: Multi-steps speed running setting
5: PID control setting
6: Remote communication setting
7: AVI2/ACI+ setting Remote communication
8: Keypad potentiometer(enabled with potentiometer)
Frequency Command Selection
Factory setting
1
00-02
Setting range
0: Available, the inverter stores parameters on power-lost
1: Available, the inverter dose store parameters on power-lost
2: UP / DOWN setting is unavailable
3: Parameter setting available on running mode, reset on stopped
4: Reserved
Keyboard and terminal UP/DOWN setting
Factory setting
2
00-01
Summary of Contents for S2800 Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 102: ......
Page 103: ......
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......