Standard One Stage Heat, One Stage Cool, Separate Fan Control, Separate
Transformers
Additional Information:
The system employs two separate transformers.
Connect one transformer to
24RC
and 2nd
transformer to
24RH
. Jumper
JP1
on circuit board
must be cut or damage to thermostat can occur.
The (
C
)ommon wire from each transformer is wired
to the
24C
terminal.
In this system there is a separate fan that can be
controlled either manually or through software on
the thermostat.
Standard Two Stage Heat, Two Stage Cool, Separate Fan Control, Separate
Transformers
Additional Information:
The system employs two separate transformers.
Connect one transformer to
24RC
and 2nd
transformer to
24RH
.
The (
C
)ommon wire from each transformer is wired
to the
24C
terminal.
Jumper
JP1
on circuit board must be cut or
damage to thermostat can occur.
In this system there is a separate fan that can be
controlled either manually or through software on
the thermostat.
SST-W100 Wireless Thermostat Deployment Guide