5.4 Control mode 4, Pressure control
The output signal will increase when the pressure signal falls below the setpoint
value.
The pressure transmitter must have an output signal of 0...10 V DC, for example:
DSU.
Pressure ranges of up to 2500 kPa kan be set.
The AO1 inverted signal is received from AO2.
DI1, Start signal
Normal control will only be activated when this input is activated, closed. When
the start signal is deactivated the controller will set the output to 0.
This input must always be wired since it controls the starting and stopping of
normal control.
Wiring example. Pressure control