System-wide functions
6
System-wide functions
6.1
Automatic summer time/winter time changeover
The clock is automatically adjusted on the last Sunday in March at 2.00h and on
the last Sunday in October at 3.00h.
Function
WE
Configuration
Summer
time/winter
changeover
time
1
CO5 -> F08 -
1
6.2
Frost protection
Frost protection measures are taken when the outdoor temperature falls below the
Frost protection limit.
The switching differential to cancel the frost protection
measures is al- ways 1 °C.
Frost protection program I (restricted frost protection): frost protection
measures are taken only when all heating circuits in the system are in stand-by
mode.
Frost protection program II: the heating circuit circulation pumps are
always swit- ched on automatically. The flow temperature set points of all heating
circuits current-
ly in stand-by mode are set to +10 °C.
Functions
WE
Configuration
Frost protection
program
I
CO5 -> F09 - 0
3.0 °C
Frost protection limit / –15.0 to 3.0 °C
Frost protection
program
II
CO5 -> F09 - 1
3.0 °C
Frost protection limit / –15.0 to 3.0 °C
NOTICE
Frost protection operation of a pump is only active when the frost protection
icon
ap- pears on the display.
In the stand-by mode ) fixed set point control without outdoor temperature
sensor does not include frost protection.
6.3
Forced operation of the pumps
When the heating circuit pump has not been activated for 24 hours, forced
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......