English
Quick Start Guide
Air velocity and temperature
transmitter
General features
Features of the housing
Used symbols
For your safety and in order to avoid any damage of the device, please follow the procedure described in
this document and read carefully the notes preceded by the following symbol:
The following symbol will also be used in this document, please read carefully the information notes
indicated after this symbol:
CTV 210-R
Connections
Electrical connections as per NFC15-100 standard
All dimensions are in millimeters.
-
+
24 Vdc
Power supply
N-
L+
N
L
24 Vac power supply
class II EN61558-2-6 standard
N-
L+
Pe
N
L
or
N
L
Power supply
N-
L+
Pe
N
L
230 Vac
230 Vac
N
L
100-240 Vac
Power supply
N-
L+
This connection must be made by a formed and qualified technician. To make the connection, the transmitter must not
be energized. Before making the connection, you must first check the power supply indicated on the transmitter board
(see (b) on “Connections” part). The presence of a switch and a circuit breaker upstream the device is compulsory.
On 100-240 Vac models, if a fuse protection is used for the power line, it is imperative to use delayed-action
fuses in order to absorb the surge of current when first turned on the transmitter.
The selection of the output signal in voltage (0-10 V or 0-5 V) or in current
(4-20 mA or 0-20 mA) is made via the DIP switch (d) of the electronic board
of the transmitter: put the on-of switches as shown in the table below:
Configurations
4-20 mA
0-10 V
0-5 V
0-20 mA
Combinations
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
•
Connection of the output in current
4-20 mA:
•
Connection of output in voltage
0-10 V:
•
For transmitters with 24 Vdc power supply:
•
For transmitters with 24 Vac power supply:
•
For transmitters with 100-240 Vac power supply:
-
+
0-5/10 V
0/4-20 mA
Regulator display or
PLC/BMS
passive type
A
4-20 mA output
-
+
0-5/10 V
0/4-20 mA
Regulator display or
PLC/BMS
passive type
V
0-10 V output
Two 4-wire analogue output
0-5/10 V or 0/4-20 mA
Airflow function
ABS V0 IP65 housing,
optional display
2 relay outputs
0-5 / 10 V
4-20 mA
Power supply
24 Vac / Vdc ±10%. 100-240 Vac, 50-60 Hz
Warning: risk of electric shock
Output
2 x 4-20 mA or 2 x 0-20 mA or 2 x 0-5 V or 2 x 0-10 V (4 wires)
Common mode voltage <30 Vac. Maximum load: 500 Ohms (0/4-20 mA). Minimum load: 1 K Ohms (0-5/10 V)
Relay outputs
2 changeover relays 3 A / 230 V. NO : 5A / NC: 3A / 240 Vac
Galvanic isolation
Inputs and outputs (models 100-240 Vac). Device fully protected by
DOUBLE ISOLATION or REINFORCED ISOLATION
Outputs (models 24 Vac/Vdc)
Consumption
CTV210-B: 6 VA. CTV210-H: 8 VA
Electrical connection
Screw terminal block for cable 2.5 mm². Carried out according to the code of good practice
PC communication
USB-Mini Din cable
Environment
Air and neutral gases
Conditions of use (°C/%RH/m)
From -10 to +50 °C. In non-condensing condition. From 0 to 2000 m.
Storage temperature
From -10 to +70 °C
Security
Protection class II; Pollution degree 2; Overvoltage category 2 (OVCII)
European directives
2014/30/EU EMC; 2014/35/EU Low Voltage; 2011/65/EU RoHS II; 2012/19/EU WEEE
Material
ABS V0 as per UL94
Protection
IP65
Display
75 x 40 mm, LCD 20 digits 2 lines.
Height of digits: Values: 10 mm;
Units: 5 mm
Cable gland
For cables Ø 8 mm maximum
Weight
340 g
1
1
5
125
59
CTV210-XXX-S-R
Power supply:
100-240 Vac
50-60 Hz 8 VA
Output:
0/4...20 mA / 0...5/10 V
100-240 Vac
24 Vac/Vdc
CTV210-XXX-S-R
Power supply:
24 Vac/Vdc ±10 %
50-60 Hz 6 VA
Output:
0/4...20 mA / 0...5/10 V
Power supply type (b) specified on the label
on the side of the transmitter
1
2
3
4
5
7
6
Analogue output 1
(out 1)
0-5/10 V
– V
oltage
GND – Ground
0/4-20 mA – Current
Analogue output 2
(out 2)
0-5/10 V
– V
oltage
GND – Ground
0/4-20 mA – Current
(a)
(c)
or
For
24 Vdc
power
supply models
-
+
(c)
or
For
24 Vac
power
supply models
Neutral (N)~
Phase (L)~
(c)
For
100-240 Vac
power supply models
Neutral (N)~
Phase (L)~
Relays 1 and 2
COM: common
NC: normaly closed
NO: normaly opened
Operating grounding
*Fuse present only for 100-240 Vac models.
Every fuse replacement must be performed witht a power off device using a TR5 630 mA 250 V fuse.
2
1. DIP switch (d)
2. LCC-S software connection
3. Relays
4. Analogue outputs (a)
5. F3.20* fuse
6. Power supply terminal block (c)
7. Cable glands