IMPORTANT:
•
The phase used to power the Mini CT Meter must match the phase being monitored by
the CT, or the meter will not generate accurate measurements.
6.
Cable of minimum cross section 0.1mm
2
and maximum cross section 1.5mm
2
(stranded) or
2.5mm
2
(solid core) may be used.
The device must be connected in the correct polarity to ensure proper operation. The Live
terminal, Neutral terminal, two Current Transformer
(CT) terminals (“CT BLACK” and “CT
WHITE”), and two SWITCH terminals are marked on the side of the device enclosure.
If the circuit being monitored is connected to a protected neutral (e.g. via an RCD), ensure
that the Mini CT Meter is also connected to the same protected neutral, and not to the main
neutral link.
Figure 2: Mini CT Meter connected to RCD protected live and neutral