Saturn South SS9007.2 Mini User Manual Download Page 13

13 

 

7

 

Metering 

As shown in Section 5, the circuit being monitored is connected directly to the SS9007 Mini CT 
Meter, providing a power supply for the device as well as enabling high accuracy voltage 
measurements. Current is measured using a clip-on current transformer (CT), with nominal primary 
current ratings of 40A and 120A available as standard. 

Each individual Saturn South meter is calibrated in the final stage of the production process. The 
calibration procedure matches each device to a particular CT variant, meaning that measurements 
will not be accurate if a device calibrated for a 120A CT is used with a 40A CT. Furthermore, given 
the wide range of secondary current ratings available for CTs, the SS9007 Mini CT Meter must only 
be used with the supplied CT.  

IMPORTANT: Attaching a third party CT to the device can damage the device and will void the 
product warranty.

 

SS9007 Mini CT Meter devices have a ‘variant label’ on the front panel that describes the rated 

primary current (and hence the CT variant to use), as well as indicating whether or not the device 
has an internal relay. For example: 

120A

” –

 Device is rated for a 120A nominal primary current. 

40A/R

” –

 Device is rated for a 40A nominal primary current and includes an internal relay. 

Max calibrated voltage 
error 

0.1% 

Max calibrated current 
error 

0.5% 

Typical absolute transfer 
ratio error for 120A CT  

< 0.5% 

Typical absolute transfer 
ratio error for 40A CT 

< 0.5% 

Region of linearity for 
120A CT (<1% error) 

8% to >110% of rated 

primary current 

Region of linearity for 
40A CT (<1% error) 

15% to >150% of rated 

primary current 

 

Figure 5: Measurement accuracy specification 

 

For a full list of measured attributes delivered by the SS9007 Mini CT Meter, please refer to Section 
8. 

 

 

Summary of Contents for SS9007.2 Mini

Page 1: ...D401 2 5 30 Dec 2015 SS9007 2 Mini CT Meter User Manual Version 5 Std HA Release build 5977...

Page 2: ...Specifications 6 5 Commissioning and Installation Instructions 7 5 1 Before Installation 7 5 2 Installation 7 5 3 Commissioning 11 6 Switching 12 7 Metering 13 8 Device Clusters and Attributes 14 8 1...

Page 3: ...ent failure This product is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience or knowledge unless they have been given super...

Page 4: ...ill join any ZigBee HA network with Permit Joining mode enabled When the button is pressed the button colour will change to yellow and then begin to rapidly blink green once is has been held long enou...

Page 5: ...ss 1 with a customizable reporting frequency of up to 1Hz Import export energy accumulations and true signed power measurements make the SS9007 an ideal choice for monitoring renewable generation sour...

Page 6: ...Range 25 C to 80 C Relative Humidity 10 95 non condensing Average Power Consumption 1W Mass 0 080kg Dimensions 60 5 x 90 x 17 5mm Wire gauge 0 1mm2 min 2 5mm2 stranded or 2 5mm2 solid core max IP Rati...

Page 7: ...Commissioning Wire the device into the switchboard as per the guidelines below and apply power 5 2 Installation The SS9007 Mini CT Meter is designed to be straightforward to install into a standard do...

Page 8: ...terminals 5 Clip the CT on to the target load conductor ensuring that the arrow on the CT points towards the load or generator away from the grid Connect the output of a MCB RCD or other protection de...

Page 9: ...connected in the correct polarity to ensure proper operation The Live terminal Neutral terminal two Current Transformer CT terminals CT BLACK and CT WHITE and two SWITCH terminals are marked on the s...

Page 10: ...monitoring 7 If your Mini CT Meter has switching capability the two terminals marked SWITCH are connected internally to an isolated relay rated for 5A at 240V The front panel button will glow amber t...

Page 11: ...econd window devices may be joined to the network by repeating step 2 If this site is being commissioned for the first time it is recommended that a factory reset be performed on the ESBox before acti...

Page 12: ...to a digital IO on a control device such as a PLC The example below shows a SS9007 Mini CT Meter being used to control an external contactor with a 240V coil by switching the active input to the conta...

Page 13: ...plied CT IMPORTANT Attaching a third party CT to the device can damage the device and will void the product warranty SS9007 Mini CT Meter devices have a variant label on the front panel that describes...

Page 14: ...not be possible for a device to send 11 attributes in a single report If the total size of the report exceeds the maximum payload size 60 bytes some attributes will be excluded from the report The de...

Page 15: ...the Simple Metering Cluster on endpoint 10 0x0A Attr ID Attr ID Hex Attribute Name Units Divisor Writeable 57610 e10a Voltage 1 RMS Mean V 100 N 57628 e11c Current 1 RMS Mean A 100 N 57646 e12e Power...

Page 16: ...mit Joining mode Try to join the device again Saturn South metering devices will initially scan a reduced subset of the full range of available ZigBee channels If the network is on a channel that is n...

Reviews: