Saturn South SS9007.2 Mini User Manual Download Page 14

14 

 

8

 

Device Clusters and Attributes 

The following Clusters are supported in the Std HA release of the SS9007 Mini CT Meter: 

 

Basic 

 

On/Off 

 

Simple Metering 

This section lists the available attributes in each supported cluster. All SS9007 ZigBee clusters are 
accessed via endpoint 0x0A. 

A maximum of 11 attributes can be configured for reporting at once. There is only one timer for 
attribute reports, and attributes will be reported at the interval specified in the most recent report 
configuration message. Because ZigBee attributes have a variable size however, it may not be 
possible for a device to send 11 attributes in a single report. If the total size of the report exceeds 
the maximum payload size (60 bytes), some attributes will be excluded from the report. The device 
will not automatically follow up with the remaining attributes if this is the case, and any missing 
attributes must be requested separately. 

8.1

 

Basic Cluster 

Cluster ID: 0x0000 (0) 
Manufacturer ID: 0x0000 (0) 

Basic information about the ZigBee node is available on endpoint 10: 

Attr ID 

Attr ID 
(Hex) 

Attribute Name 

Writeable 

ZigBee Cluster Library Version 

Application Version 

Stack Version 

Hardware Version 

Manufacturer Name 

Model Identifier 

Date Code 

Power Source 

16 

10 

Location Description 

18 

12 

Device Enabled 

 

 

 

Summary of Contents for SS9007.2 Mini

Page 1: ...D401 2 5 30 Dec 2015 SS9007 2 Mini CT Meter User Manual Version 5 Std HA Release build 5977...

Page 2: ...Specifications 6 5 Commissioning and Installation Instructions 7 5 1 Before Installation 7 5 2 Installation 7 5 3 Commissioning 11 6 Switching 12 7 Metering 13 8 Device Clusters and Attributes 14 8 1...

Page 3: ...ent failure This product is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience or knowledge unless they have been given super...

Page 4: ...ill join any ZigBee HA network with Permit Joining mode enabled When the button is pressed the button colour will change to yellow and then begin to rapidly blink green once is has been held long enou...

Page 5: ...ss 1 with a customizable reporting frequency of up to 1Hz Import export energy accumulations and true signed power measurements make the SS9007 an ideal choice for monitoring renewable generation sour...

Page 6: ...Range 25 C to 80 C Relative Humidity 10 95 non condensing Average Power Consumption 1W Mass 0 080kg Dimensions 60 5 x 90 x 17 5mm Wire gauge 0 1mm2 min 2 5mm2 stranded or 2 5mm2 solid core max IP Rati...

Page 7: ...Commissioning Wire the device into the switchboard as per the guidelines below and apply power 5 2 Installation The SS9007 Mini CT Meter is designed to be straightforward to install into a standard do...

Page 8: ...terminals 5 Clip the CT on to the target load conductor ensuring that the arrow on the CT points towards the load or generator away from the grid Connect the output of a MCB RCD or other protection de...

Page 9: ...connected in the correct polarity to ensure proper operation The Live terminal Neutral terminal two Current Transformer CT terminals CT BLACK and CT WHITE and two SWITCH terminals are marked on the s...

Page 10: ...monitoring 7 If your Mini CT Meter has switching capability the two terminals marked SWITCH are connected internally to an isolated relay rated for 5A at 240V The front panel button will glow amber t...

Page 11: ...econd window devices may be joined to the network by repeating step 2 If this site is being commissioned for the first time it is recommended that a factory reset be performed on the ESBox before acti...

Page 12: ...to a digital IO on a control device such as a PLC The example below shows a SS9007 Mini CT Meter being used to control an external contactor with a 240V coil by switching the active input to the conta...

Page 13: ...plied CT IMPORTANT Attaching a third party CT to the device can damage the device and will void the product warranty SS9007 Mini CT Meter devices have a variant label on the front panel that describes...

Page 14: ...not be possible for a device to send 11 attributes in a single report If the total size of the report exceeds the maximum payload size 60 bytes some attributes will be excluded from the report The de...

Page 15: ...the Simple Metering Cluster on endpoint 10 0x0A Attr ID Attr ID Hex Attribute Name Units Divisor Writeable 57610 e10a Voltage 1 RMS Mean V 100 N 57628 e11c Current 1 RMS Mean A 100 N 57646 e12e Power...

Page 16: ...mit Joining mode Try to join the device again Saturn South metering devices will initially scan a reduced subset of the full range of available ZigBee channels If the network is on a channel that is n...

Reviews: