Control “MONO” output
[MONO outs ctr.] – if this option is enabled, the ““Mono” output
operating” type of users can use the keypad to control outputs.
Partition blocking
[Part.blocking] – if the option is enabled, using the code by a user of the
“Blocking partition” or “Guard” type will block the armed partition (violating a zone
belonging to the partition will trigger no alarm). The duration of blocking is to be defined for
the partition or the user (the user of “Blocking partition” type).
Guard round control
[Guard control] – if this option is enabled, using the code by a user of
the “Guard” type will be registered as the guard round.
Changing access code
[Changing code] – if this option is enabled, the user can change
own code from the partition keypad.
Exit delay clearing enable
[Fin.exit time] – if the option is enabled, the user can terminate
the partition exit delay countdown by pressing successively
and
(if the “Exit
delay clearing” option is enabled for the partition).
Alarm signal
[Alarm (time)] – if this option is enabled, the keypad will audibly signal alarms
throughout the “Global alarm time” (parameter programmed in the control panel).
Alarm signal (until canceled)
[Alarm (latch)] – if this option is enabled, the partition keypad
will audibly signal alarms until they are cleared.
Sign. entry delay
[Entry time] – if this option is enabled, the partition keypad will audibly
signal the entry delay countdown.
Sign. exit delay
[Exit time] – if this option is enabled, the partition keypad will audibly signal
the exit delay countdown.
Auto-Arm delay countdown
[Auto-arm delay] – if this option is enabled, the partition keypad
will audibly signal the auto-arm delay countdown.
Acc. code sign. (hardware)
[Code entered] – if this option is enabled, the partition keypad
will confirm with a single beep that the code has been entered. The signaling is useful
when there is a delay between entering the code and the sounds emitted after verification
of the code by the control panel.
CHIME
[Chime zones] – if this option is enabled, the partition keypad will audibly signal
violation of zones with “Chime in module” option enabled, belonging to the partition
operated by means of the keypad.
No auto-reset after 3 tamp.
[No autorst.3t.] – if this option is enabled, the feature reducing
the number of tamper alarms from the module to three is disabled (the feature prevents
multiple logging of the same events and applies to successive uncleared alarms).
Backlight
– keys backlight operation mode:
No
– always off.
Auto
– on for about 40 seconds after pressing any key. Additionally, it can be turned on if
a specific event occurs (see the “Auto-backlight”
parameter).
Permanent
– always on.
Auto-backlight
– if the keys backlight comes on automatically, you can additionally define
whether and what event will turn the backlight on:
No
– the keys backlight will not be additionally turned on.
Zone violation
– the keys backlight will additionally go on if a selected zone is violated.
Entry delay, part.
– the keys backlight will additionally go on if entry delay countdown
starts in the selected partition.
Unlock door if fire
[Doors on fire] – you can define whether and when the fire alarm will
unlock the door controlled by the partition keypad (i.e. will activate the relay output):
No
[no open] – the door will not be unlocked in the event of fire alarm.